Case: T04DV00995

Parcel: 111070160


Addresses:

3434 E WATER ST #21


Inspection Status: Correction Required

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T04DV00995

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/10/2005 INSP - INITIAL CODE ENFORCMENT Correction Required 2/10/05
VISITED SITE TO RE-INSPECT ELECTRICAL SHEDS. INSPECTOR HURD WANTED VERIFICATION FROM INSPECTOR ORTA ON MULTIPLE CODE VIOLATIONS.SEVERAL SHEDS/PANELS WERE INSPECTED.VIOLATIONS WERE AS FOLLOWS:
MAIN ELECTRICAL ENTRANCE SHED:
(1) MAIN SERVICE PANEL NOT IDENTIFIED AS WELL AS (7) SUB-PANELS.
(2)CLEARANCE IN ELECTRICAL SHED INSUFFICIENT, MINIMUM 36" CLEARANCE, SHED HAS ONLY 30" CLEARANCE.
(3)MAIN 400 AMP DISCONNECT NOT BONDED TO ENCLOSER, NEEDS MAIN BONDING JUMPER.
(4)BUSHINGS MISSING IN VARIOUS PANELS
(5)NEW PANEL ADDED, POSSIBLY WITHOUT PERMITS
(6)BOXES NOT RAIN TIGHT
(7)DOOR ON FAR LEFT PANEL UNABLE TO OPEN 90 DEGREES
(8) KNOCK OUTS MISSING ON SEVERAL PANELS
(9)DILAPIDATION AND CORROSION EVIDENT IN SEVERAL PANELS
(10) PANEL #3 (CHECK INSPECTION REQUEST FORM FOR OUR PANEL LISTING); CURRENT PROTECTION FOR WIRE SIZE OVER FUSED
(11)PANEL #5 DOUBLE LUGGED
(12)UNSURE OF COLOR CODING METHODS OF NUETRAL WIRES
AT PANEL #7
(13)OVER FUSING OF CONDUCTORS #6
(14) BREAKER EXCEDING UL LISTING, CIRCUIT NOT TO EXCEED 110 AND IS BONDED, AND SHOULD NOT BE BONDED AT PANEL #4

SOUTHWEST SHED/PANEL:
(1) SHED HAS CLEARANCE PROBLEM, DOES NOT MEET MINIMUM CLEARANCE
(2)NEEDS LOAD CALCS.
(3)BOXES NOT IDENTIFIED
(4) DOUBLE LUGGING IN ONE OF THE BOXES
(5)WIRES DO NOT MEET MINIMUM BENDING RADIOUS
(6) OVER FUSED 100 AMP ON #10 WIRE
(7) IMPROPER GROUNDING, OR NO GROUNDING AT ALL

GARAGE/STORAGE SHOP:
(1)WIRE NUTS TOO SMALL FOR APPLICATION
(2) ARCHITECTUAL HINDERANCE; BLOCK WALL POP-OUT DOES NOT MEET MINIMUM CLEARANCE
(3)EQUIPMENT GROUND IS INCORRECT COLOR AND TYPE
(4) BACK FED MAIN REAKER REQUIRES A MAIN BREAKER RETAINER CLIP
(5)MIXED BREAKERS DO NOT COMPLY WITH LISTINGS
02/01/2005 INSP - INITIAL CODE ENFORCMENT Correction Required 1/31/05
VISITED SITE, TOOK PICURES, UPON ARRIVAL STOPPED AT OFFICE,MANAGER CARLOS WAS OUT. CALLED CARLOS, WHO MET US ON SITE, WALKED UNIT 21, VACANT. PARK IS SELLING UNIT, FOUND ADDITION TO SOUTH SIDE. CEILING DOES NOT MEET 7FT. HEIGHT, AND NO PERMANENT SOURCE OF HEAT. OUTLET IN ADDITION NOT PROPERLY SECURED TO WALL. SUB-PANEL IN CLOSET HAS NEWLY EXPOSED ROMEX. EXPOSED ABS SEWER LINE. ELECTRICAL PANEL BOX MISSING COVER PLUG. OUTSIDE MAIN 40 AMP CORD TO INTERIOR 50 AMP SUB-PANEL. JUST TO NORTH OF #21 IS SHED, SHED HOUSES ELECTRICAL MAATER PANEL, REAR ENTRANCE HAS OPEN JUNCTION BOX, WIRE SPLICED, NUTURAL GOES NO WHERE, CUTAND OPEN-EXPOSED.INTERIOR OF SHED HAS 3 100 AMP SERVICES, SHOWS 28-15-16-17 . FUSE BOX TO LOWER RIGHT SHOWS 2 FUSES 30 AMP USING 14 GUAGE WIRE TO SUPPLY WIRE. HOTWATER TANK OPEN EXPOSED, GAS NOT ACCESSABLE, NO COLD WATER EMERGENCY SHUT OFF, NO P.R.V. INSTALLED, UNIT HAS HAD ALL NEW P.V.C. LINES INSTALLED.
UNIT 22:
ELECTRICAL METER HARD WIRED TO STRUCTURE, 2-50 AMP, 1 30 AMP, 1 15 AMP, INSTALLED AT METER BOX, EXPOSED WIRING 2 TIMES, 1 GOING INTO GROUND? 1 HARD WIRED TO MOBILE HOME FOR SALE, HOTWATER TANK LACKS P.R.V., NO COLD WATER SHUT-OFF,FLUE PIPE SHORT AND DOES NOT GO ABOVE ROOF LINE. GAS METER IN FRONT OF STRUCTURE HAS BENT GAS LINE. METER IS NOT PROTECTED FROM POSSIBLY BEING HIT BY CARS. BACK DOOR HAS NO STEPS. TREE IS HITTING AND LAYING ON TOP OF MOBILE HOME.

UNIT #24
PLUMBING VENT PIPE NOT SECUREDTO STRUCTURE AND IS TOO SHORT. ADDITION ADDED TO SOUTH SIDE OF STRUCTURE. EXPOSED ROMEX TO LIGHT LAYING ON GROUND, AND BEING PINCHED BETWEEN SIDING AND FRAMING. ELECTRICAL METER SHOWS IT IS HARDWIRED IN. EXPOSED ROMEX , 2LINES 1 METER 50 AMP AND 1 20 AMP, ALSO HAS OPEN SPACE. PLUMBING ABOVE GROUND TO SITE SEWER. HOTWATER TANK FLUE PIPE TOO SHORT. SUB-PANEL REVERSED POLARITY, WIRES TOUCHING EACH OTHER AT CONNECTIONS. SOME 3 PRONG OUTLETS SHOW OPEN GROUND.

MAIN ELECTRICAL SHED:
MAIN 400 AMP SERVICE DOUBLE LUGGEDON LOAD SIDE, DOUBLE LUGGED ON DISCONNECT SIDE.DOUBLE LUGGED WIRES LOOSE AND CAN BE PULLED OUT. EXPOSED WIRING AT REAR SHED.

UNIT #50
HARDWIRED EXPOSED ROMEX, OPEN ONE END AND ACTIVE.

AFTER WALKING 3 UNITS AND THE MAIN ELECTRICAL SHED WE DECIDED TO FIRST WALK THE ENTIRE PARK TO FIND OUT THE SITUATION OF THE UNITS. WE FOUND THAT MOST UNITS,THERE ARE APPROXIMATELY 60 UNITS, HAD MULTIPLE CODE VIOLATIONS, AND THERE WERE SEVERAL UNITS WITH ADDITIONS PROBABLY NOT PERMITTED.AT THAT TIME WE CALLED INSP 2 (RICK) WENT OVER ISSUES AND AGREED NOT TO DO THE ENTIRE PARK AT THIS TIME DUE TO FACT THERE ARE SO MANY UNITS ON SITE. INSPECTOR 2 REQUESTED WE COME BACK TO OFFICE TO REVIEW CASE, NOTES AND PICTURES.
AT THIS TIME IN PROCESS OF REVEIWING CASE WITH INSP. 2