Case: T04DV00971

Parcel: 11006012C

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T04DV00971

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2005 INSP - INITIAL CODE ENFORCMENT Approved VISITED SITE TENANT FILING COMPLAINT, NO LONGER IN UNIT, MADE CONTACT WITH MANAGER, BILL & STATED NEW TENANT HAS DONE MANY REPAIRS TO INTERIOR & EXTERIOR, NEW PAINT THROUGHOUT & NEW ROOF, INSTALLED CEILING IN KITCHEN BUT LACKS FINISHING. DID FIND MIN-HOUSING ISSUES & ARE AS FOLLOWS
ELECTRICAL;
1) MAIN SYSTEM HAS BEEN UP-GRADED ALONG WITH INTERIOR CIRCUT. INTERIOR CIRCUTS & ALL TESTED CORRECTLY. ALL EXTERIOR CONNECTIONS ARE WEATHER TIGHT. CHECK FOR PERMITS.
2) DID FIND DOUBLE LUGGING IN DISCONNECT BOX
3) ILLEGAL SPLICED ELECTRICAL CONDUCTOR FOR HWH
4) G.F.I.C. LACKING FOR KITCHEN

WEATHER PROOFING;
1) BACK DOOR LACKS WEATHER STRIPPING
2) BROKEN & BOARDED UP WINDOW ON EASTSIDE

ACCESS CONTROL;
1) DOUBLED KEYED DEAD BOLT ON BACK DOOR.

PLUMBING;
1) MODIFICATION TO VENT SYSTEM, PICTURES WERE TAKEN.

FIRE SAFETY;
1) LACK REQUIRED SMOKE DETECTORS.
NOV TO BE ISSUED AFTER RESEARCH FOR ELECTRICAL UPGRADE