Case: T04DV00940

Parcel: 123152740

Inspection Status: Correction Required

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Case Number - T04DV00940

Inspection Description - INSP - FOLLOW UP CODE ENFORCE

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/23/2005 INSP - FOLLOW UP CODE ENFORCE Correction Required WENT TO D.S.D AND TALKED WITH NEIL RESIDENTIAL DESK, WENT THROUGH ISSUES, BASICALLY HAD TO TALK TO CHRISTINE AT COMMERICAL STRUCTURAL, TALKED WITH CHRISTINE WHO AGREED THERE IS A ISSUE, CHRISTINE CALL OVER JASON (BEHIND DESK) WHO WENT THROUGH ISSUES STATED HE WILL NEED TO GET WITH STEVE LONG TO SEE WHERE WE ARE GOING.
06/01/2005 INSP - FOLLOW UP CODE ENFORCE Correction Required 5/26/05, VISITED SITE, APPT., INSP. ORTA ASST. MEET WITH OWNERS FATHER WENT THROUGH UNITS 1,3,6 TO SEE IF ANY ELECTRICAL HAZARDS EXSIST ON INTERIOR.
UNIT 1-
EXTERIOR SERVICE PANEL MISSING FRONT DEAD PLATE,
NO MAIN GROUNDING ELECTRODE SYSTEM FOR SEPERATE BUILDING.
LACKS PROTECTIVE PLASTIC BUSHINGS FOR #2 FEEDER.
ONE FEEDER COMMING IN FROM DOUBLE LUGGING AND HAS FEEDER GOING OUT TO UNKNOWN LOCATION.
INTERIOR:
LIVING ROOM CONVENIENCE OUTLET SHOWS OPEN GROUND UNDER TEST.
CONVENIENCE OUTLET IN DINING ROOM AREA LOOSE AND WORN.
LACKS GFCI PROTECTION.
REFRIGERATOR CASING SHOWS ENGERIZED VOLTAGE, SHOCK HAZARD.
UNIT 3: VACANT AT THIS TIME:
LIVING ROOM CONVENIENCE OUTLET SHOWS OPEN GROUND UNDER TEST.
CONVENIENCE OUTLET BROKEN.
CONVENIENCE OUTLET IN KITCHEN AREA COUNTERSUNK INTO WALL.
SUB-PANEL IN CLOSET.
SUB-PANEL SHOWS DOUBLE LUGGING ON LOAD SIDE.
SUB-PANEL SHOWS DOUBLE LUGGING ON DISCONNECT SIDE ON 2 SEPERATE BREAKERS.
LACKS EQUIPMENT GROUND TO BRANCH CIRCUITS.
KNOCK OUT PLUGS MISSING.
NO STRAIN RELIEF FOR CONDUCTOR ENTERING SUB-PANEL.
DOUBLE LUGGING ON NETURAL BAR.
UNIT 6:
MINIMUM CONVENIENCE OUTLET SPACING HAS BEEN EXCEEDED.
NO STRAIN RELIEF ON FEEDER AT PANELBOARD.
PANELBOARD IN CLOSET.
CONVENIENCE OUTLET BY FRONT DOOR SHOWS OPEN GROUND UNDER TEST.
ALL CIRCUITS LACK PROPER IDENIFICATION.
COLOR CODE OF WIRES MIXED NOT PROPERLY I.D..
IMPROPERLY INSTALLED ROMEX.
OPEN ROMEX.
IMPROPER TERMANATION OF BATHROOM LIGHT FIXTURE.
SMOKE DETECTOR LOCATED IN WRONG AREA.
REQUIRED KITCHEN COUNTER CONVENIENCE OUTLETS NOT INSTALLED.
12/02/2004 INSP - FOLLOW UP CODE ENFORCE Approved 12/02/04 WHEN TALKING WITH MANAGER, ASTATKE, HE STATED THAT HE WOULD MEET ME ON SITE 12/2/04, AT 2:00PM WITH HEATING CONTRACTOR. VISITED SITE, WAITED UNTIL 2:30 PM ASTATKE NOR CONTRACTOR SHOWED UP ON SITE. LEFT SITE AT 2:30 PM, WENT TO ASTATKE'S HOME ON 15TH ST. AND HAND DELIVERED NOV TO ASTATKE, WENT OVER ISSUES ON NOTICE AND ORDER INCLUDING TIME FRAME. ASTATKE WAS NOT HAPPY TO SEE ME, SIGNED FOR NOV AND WENT INTO HOUSE. LEFT SITE.