Case: T04DV00789

Parcel: 118121360


Addresses:

304 E 23RD ST

Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Date Description Inspector Results Comments
03/31/2006 INSP - FOLLOW UP CODE ENFORCE Approved VISITED SITE ON FOLLOW UP INSPECTION, STRUCTURE IS STILL VACANT. STRUCTURE WAS FOUND SECURED, LOCKS AND CHAINS ON GATES. APPEARS REHAB WORK IS STILL GOING ON EVIDENCED BY NEW ANS SEWER VENT DRAIN ON WEST SIDE OF STRUCTURE. ATTEMPTED CONTACTING OWNER FOR STATUS, MAIL BOX WAS FULL AND ALLOWED ONLY CONTACT NUMBER TO BE LEFT. LEFT CELL NUMBER FOR RETURN CALL REGARDING STATUS OF NOV ISSUES REMAINING.
02/22/2006 INSP - FOLLOW UP CODE ENFORCE Approved VISITED SITE ON FOLLOW UP INSPECTION. MET WITH OWNER, WHO HAS DECIDED TO SELL THE PROPERTY AND STATED HE WILL ABATE ALL THE ISSUES ON THE NOV. WENT OVER ISSUES , MY FINDINGS ARE AS FOLLOWS:
1)TC 16-11 BUILDING INTERIORS (A) FIRE SAFETY, 3
VIOLATION ABATED- NEW SMOKE DETECTORS INSTALLED

2)TC 16-11 BUILDING INTERIORS (A) FIRE SAFETY 1& 3
VIOLATION ABATED- WINDOW CRANKS REPLACED

3)TC 16-11 BUILDING INTERIORS (B) HEATING SYSTEMS TC 16-4 PERMITS REQUIRED
1) NOT ABATED- MAKING ARRANGEMENTS TO SECURE COMBO PERMIT
2) NOT ABATED- WORK IN PROCESS
3) ABATED- ALL ITEMS STORED IN FURNACE CLOSET WERE REMOVED

4) TC 16-11 ELECTRICAL SYSTEMS 1& 2 TC 16-4 PERMITS REQUIRED
1)NOT ABATED- 3 PRONG RECEPTICLES TO BE REPLACED
2)NOT ABATED- PLANS TO INSTALL GFCI
3)ABATED NEW COVER PLATE INSTALLED
4)VIOLATION ABATED- VIOLATION REMOVED
5)VIOLATION ABATED- UPGRADE HAS BEEN COMPLETED AND PERMIT T06EL06223 WAS FINALED ON 2-9-06

5)TC 16-11 BUILDING INTERIORS (D) MECHANICAL EQUIPMENT
VIOLATION ABATED- NEW COVER AND EXHAUST FAN MOTOR REPAIRED

6) TC 16-11 BUILDING INTERIORS (E) PLUMBING SYSTEMS 2 + 3
TC 16-4 PERMITS REQUIRED
1 NOT ABATED ENCLOSURE TO BE INSTALLED
2 NOT ABATED NEW PIPING TO BE INSTALLED UNDER PERMIT AND HAS REMOVED PIPING IN VIOLATION
3 ABATED VIOLATION REMOVED AND PLANS TO INSTALL CORRECT PLUMBING UNDER PERMIT
4 ABATED NEW COUNTER TOP FOR SINK HAS BEEN INSTALLED
7) TC 16-11 BUILDING INTERIOR FEATURES 3+ 4
1 NOT ABATED DOOR NEEDS TO BE REPLACED
2 NOT ABATED FLOOR NEEDS TO BE REPLACED
8)TC 16-12 BUILDING AND STRUCTURES EXTERIOR A WEATHER STRIPPING VIOLATION ABATED, NEW WINDOWS INSTALLED AS WELL AS WEATHER STRIPPING FOR FRONT DOOR.

OWNER MAKING GOOD PROGRESS WILL EXTEND ABATEMENT PERIOD 30 DAYS.
01/25/2006 INSP - FOLLOW UP CODE ENFORCE Approved VISITED SITE ON FOLLOW UP INSPECTION, STRUCTURE WAS FOUND VACANT. BOTH ENTRY GATES ARE CHAINED AND LOCKED WITH PAD LOCKS. NO TRESPASSING SIGNS ARE POSTED. ATTEMPTED CONTACTING TENANTS, BOTH NUMBERS ARE OUT OF SERVICE, ATTEMPTED CONTACT WITH OWNER BY PAGER NUMBER ON FILE, NUMBER IS ALSO OUT OF SERVICE. WILL CHECK OFFICE RECORDS FOR OTHER NUMBERS. WILL ADVICE INSPECTOR 2 OF REQUEST FOR REMOVAL OF ELECTRIC METER FROM TEP AND REQUEST CONTACT BY TEP BEFORE POWER IS RESTORED TO STRUCTURE. NO PICTURES DUE TO DEAD BATTERIES IN CAMERA.

RESEARCH IN PERMITS PLUS SCREEN SHOWS NO CURRENT PERMIT IS REQUESTED ON NOV ISSUED ON 11/10/2005.

INSPECTOR 2 WAS EMAILED FOR A RESPONSE.
08/19/2005 INSP - FOLLOW UP CODE ENFORCE Approved MET WITH OWNER ON SITE FOR FW/UP COMPLIANCE INSPECTION FOR N.O.V. ISSUED BY INSP. JESS CRAIG. COVERED ISSUES AND FOUND OTHER VIOLATIONS NOT LISTED ON N.O.V. N.O.V ISSUES LISTED ON N.O.V ISSUED ON 9/29/04.
1. T.C. 16-11-A2 FIRE SAFETY.
NOT ABATED- WINDOW CRANK HARD TO OPEN.
SMOKE DETECTORS.
T.C 16-11-A3, NOT ABATED, NO WORKING SMOKE DETECTOR, OWNER HAS SUPPLIED NEW SMOKE DETECTORS AND WILL BE INSTALLING BY THIS WEEKEND.
HEATING
T.C. 16-11-B1 HALF WAS ABATED, T-STAT HAS BEEN REPLACED. FURNANCE HAS BEEN REPLACE WIT NEW TYPE, NEW GAS LINES AND VALVES. RESEARCH IN PERMITS PLUS SCREEN, FOUND NO APPROVED PLANS NOR PERMITS FOR NEW TYPE OF FURNACE INSTALLATION. WILL CHECK RECORDS AT D.S.D BEFORE AMENDED N.O.V IS SENT-OUT.
COOLING
T.C. 16-11-B2. ABATED COOLER PROBLEM WAS REPAIRED.
INTERIOR FEATURES:
T.C. 16-11-F ( 3&4)
1- NOT ABATED, SHOWER REPAIRED, SINK IS BROKEN AND HELD TOGETHER BY CALKING AND IS NOT ATTACHED TO WALL. 3'' GAP BETWEEN WALL AND CABINET.
2- ABATED. NEW KNOBS WERE INSTALLED.
PLUMBING
T.C. 16-11-E3
1- ABATED. SHOWER WALL REPAIRED
2- ABATED. DRAIN SYSTEM CLEARED
3- ABATED. BATHROOM AND KITCHEN FAUCET HANDLE WERE REPAIRED AND NO LONGER LEAKING.
4- ABATED. HOT WATER HAS BEEN RESTORED.
WEATHER PROTECTION/ PROTECTIVE TREATMENT
1- NOT ABATED. ENTRY DOOR STILL LACKING WEATHER PROTECTION. BROKEN WINDOW IN BEDROOM.
OTHER ISSUES WERE FOUND ON INSPECTION AND ARE AS FOLLOWS:
ELECTRICAL
1- SEVERAL 3 PRONG RECEPTUCLES WERE TESTED AND FOUND TO BE INSTALLED IN A HAZARDOUS MANNER, SOME WERE LACKING EQUIPMENT GROUND, REVERSED NOT MATERAL. APPEARS ELECTRICAL SYSTEM WAS WIRE 60 AMP SERVICE. UP- GRADE TO 100 AMP HAS BEEN STARTED AND PERMIT # T99EL00391 EXPIRED ON 3/1/99.
2- GFCI IN KITCHEN AND BATHROOM, BATHROOM FIXTURE HAS UNGROUNDED RECEPTACLE.
3- LIGHT SWITCH COVER PLATE MISSING IN BEDROOM, AS WELL AS KNOB.
4- 220 CIRCUIT HAS BEEN INSTALLED IN A HAZARDOUS MANNER, NOT INSTALLED IN REQUIRED CONDUCT,
PLUMBING
1- NEW TYPE GAS LINES HAVE BEEN INSTALLED FOR FURNACE, EXTERIOR GAS LINES ARE NOT SECURED PROPERLY, CHECK FOR PERMITS.
2- ADDITION OF A.B.S PIPING FOR WASHING MACHINE AND FOR KITCHEN SINK DRAIN, APPEARS NOT TO HAVE BEEN INSTALLED UNDER PERMITS. EVIDENCED BY LARGE SECTION. NOT SECURED TO WALL, TEMORARY COUPELING HAS BEEN INSTALLED. CHECK FOR PERMITS.
3- T.R.P DRAIN HAS NOT BEEN INSTALLED PROPERLY. DOES NOT EXTEND DOWNWARD TO TERMINATE 6 INCHES ABOVE FINISHED FLOOR.
4- BATHROOM SINK HAS NOT BEEN MAINTAINED. SINK IS BROKEN AN DHELD TOGETHER BY CAULK. SINK CABINET NOT ANCHORED TO WALL. HAS 3'' OPENING.
INTERIOR FEATURES
1- BACKDOOR LACKS LOCKING MECHINISM, AND DOES NOT CLOSE PROPERLY WITHOUT USING FORCE.
2- KITCHEN FLOOR BETWEEN BEDROOM HAS NOT BEEN COMPLETED.
ACCESS CONTROL
1- DEADBOLT, DOUBLE KEYED CYLINDERS HAVE BEEN INSTALLED ON EXIT DOOR FROM KITCHEN AND LIVING ROOM.
MECHANICAL SYSTEM
1- EXHAUST FAN MISSING VENT COVER.
PICTURES WERE TAKEN. INFORMED OWNER, HE WOULD HAVE 30 DAYS TO COMPLETE ITEMS FROM N.O.V ISSUED BY INSP. CRAIG AND ORIGINAL N.O.V WILL BE AMMENDED TO INCLUDE VIOLATION FOUND AND OR MISSED ON PREVIOUS INSP.
07/22/2005 INSP - FOLLOW UP CODE ENFORCE Approved VISITED SITE ON FW/UP INSPECTION, ATTEMPTED MAKING CONTACT WITH OCCUPANT. PROPERTY POSTED NO TRSESSPASSING & BOTH FRONT & BACK GATES WERE SECURED WITH LOCKS & CAHIN. RINGER IS MONTED ON FENCE POLE BY GATE, RANG SEVERAL TIMES & HAD NO RESPONSE. APPEARS STRUCTURE HAS BEEN PAINTED & NEW WEATHER HEAD WITH DISCONNECT (ELECTRICAL) HAS BEEN INSTALLED, BUT NOT CONNNECTED TO ELECTRICAL SERVICE. CONTACTED SUPPORT STAFF TO VERIFY CURRENT OWNERSHIP. NOV HAD BEEN ISSUED & RECORDS SHOW SAME OWNER. RECEIVED PHONE NUMBER FROM SUPPORT STAFF OUT OF PHONE BOOK. ATTEMPTED CONTACT, NO ANSWER, LEFT MESSAGE FOR MR. CARL & OR CARLTON BOWDRY INFORMING HIM DNR INSP. WAS ON SITE TO DO FW/UP ON NOV ISSUE, LEFT CELL # & REQUESTED RETURN CALL FOR SCHEDULING OF INSP. TOOK PICTURES APPEARS W/O/P ON SEWER DRAIN SYS. & EXPIRED ELECTRICAL PERMITS WERE NOT ADDRESSED BY INSP. JESS CRAIG ON NOV ISSUED ON 9-29-04. WILL GO OVER CASE WITH INSP 2 RICK SALDATE & AWAIT CONTACT BY OWNER. DO FOLLOW UP IN 15 DAYS.