Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T04DV00767
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INSPECTION SCHEDULED FOR 9/28/04 WITH TENANT. TESTED CIRCUIT IN LIVINGROOM TEST CORRECT WIRING. CIRCUIT IN KITCHEN NO POWER. BEDROOM CIRCUIT TESTS CORRECT WIRING. INSPECTED MAIN SERVICE METER. NO VIOLATIONS FOUND. EXPOSED WIRING FOUND TO EXTERIOR LIGHT FIXTURE ABOVE MAIN SERVICE PANEL UNDER 8' IN HEIGHT. SMOKE DETECTOR MISSING BATTERY. MET IN OFFICE ASSISTANT MANAGER GAVE COPY OF NECESSARY REPAIRS. MET WITH MAINTENANCE INFORMED HIM OF NEEDED REPAIRS. |