Case: T04DV00708

Parcel: 111070200


Addresses:

3339 E GRANT RD


Inspection Status: Correction Required

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Case Number - T04DV00708

Inspection Description - INSP - FOLLOW UP CODE ENFORCE

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/29/2004 INSP - FOLLOW UP CODE ENFORCE Correction Required I MET JERRY ORTA FROM DSD AT SITE TO REVIEW ENTIRE ELECT. SYSTEM IN PARK:
THE FOLLOW ISSUE'S HAVE BEEN FOUND AND THE FOOLOWING ACTION WILL TAKE PLACE.
THE ENTIRE PARK WILL BE REQUIRE TO HAVE A FULL ELECT. UPGRADE -INCLUDING ALL PEDESTALS -LIFE LINES AND MAIN PANELS, INCLUDING SUB-PANELS WILL REQUIRE REPLACEMENT.
THE CURRENT SYSTEM IS UNDER AMP AND HAZARDOUS AND IMPROPER DUE TO POOR WORKMANSHIP AND PLACEMENT OF SUB-PANELS AND TYPE OF CONTIONS FOUND CONCERNING EACH UNIT.
THE SYSTEM HAS BEEN FOUND TO HAVE THREE AREAS WHERE POWER IS PULLED INTO THE PARK, (3) LOCATIONS IN THE PARK ARE IN THE CENTER-EAST SIDE FRONT AND THE REAR SIDE RIGHT.
THE CURRENT SYSTEM IS A TOTAL OF 600 AMPS- THE PARK IS REQUIRED TO HAVE 800 AMPS DUE TO SIZE AND THE AMOUNT OF DEMAND PER UNIT. 1600 VOLT AMPS PER SPACE BY 240 VOLTS BY A DEMAND FACTOR OF 45% BY .45 = A REQUIRED SERVICE OF 800 AMPS, THIS WILL REQUIRE THE PROPERTY OWNER TO DRAW PLANS WITH A ENG.STAMP APPROVAL FOR DSD. THIS PARK WILL NOT BE ALLOWED TO MADE GEN. REPAIRS. THE PARK HAS A LONG STANDING HISTORY WITH DSD AND ELECT. PROBLEMS WITH OUT PROPER ABATEMENT.
THERE HAS BEEN ISSUE'S FOUND OF BARE WIRES- SUB-PANEL HEIGHTS, SHUT-OFF HAZARDS, UNDER AMP SERVICE. LOW SERVICE WIRES TO UNITS, OVER LOADING SYSTEM, W/O PERMIS ENTIRE PARK ELECT. SYSTEM.
PEDSETALS SHORTER THAN 24 ''.
SERVICE WIRES BELOW THE ALLOWED 8 '.
ALL THESE ISSUE'S WILL REQUIRE A NOTICE AND ORDER.
AT SOME POINT THE ENTIRE PARK WILL BE SHUT-DOWN PENDING ABATEMENT.NOTICE AND ORDER UNDER REVIEW BY SUPERVISOR C-2.