Inspection Status: Correction Required
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T04DV00614
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | 8/16/04, REVISITED SITE TOOK PICTURES, MET WITH T.F.D. INSP. WAYNE CUMMINGS, BEGAN INSP. ON EXTERIOR BUILDINGS 2,3. FOUND SEVERAL ISSUES LISTED BELOW. | |
| 08/16/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP BLD 3 - EXTERIOR C-13 BUILDING (3) 1ST FLOOR PAINT CHIPPING AND FLAKING. POST BY UNIT 7 BASE DETERIORATED (TERMITES). HEADER MOVING LEANING OUTWARD. UNIT 10 HOT WATER TANK MISSING B-VENT AND FLUE PIPE, ADDED ELECTRICAL CIRCUIT FROM WALL TO LIGHT FIXTURE. SOUTHEND EXPOSED ELECT. LIGHT FIXTURE HANGING FROM WALL. MASTER PANEL TOP BOX SEPERATING FROM WALL, NOT LABELED REAR BLOCK WALLS, (PONY WALLS). REAR BUILDING ADDED ELECTRICAL CIRCUIT LIGHT FIXTURE. UNIT 12 - BALCONY ABOVE FLOOR DETERIORATING - PORCH ROOF DETERIORATING PLASTER CRUMBLING, SUPPORT POST CONNECTIONS. UNIT 12 EXPOSED OUTLET, UNIT 12 SUPPORT POST THAT RUNS FROM 2ND FLOOR TO GROUND IS BEING PUSHED OUT OF PLUMBING, APPROX. 3", POST COMMING OFF BASE. METERS MIDDLE BACKER BOARD DETERIORATING, METERS NOT LABELED. EAVE PLASTER CRUMBLING AND FALLING. DETERIORATING METERS NORTH END BOARD DETERIORATING. NEEDS PAINT, NOT LABELED. 2ND FLOOR RAILING SEPERATING FROM DECK. DECK (EAST-WEST) DETERIORATING, ROTTING WOOD, BOARDS, RAILING SUPPORT POST - SCREWS RUSTED, NOT SECURING POST - WOOD DETERIORATED ALL 2ND FLOOR RAILING 30" HEIGHT. RAILING LOOSE WEST SIDE. LIGHT FIXTURE COMING AWAY FROM WALL, EXPOSED BOX UNIT 22 SUPPORT POST DETERIORATED, WOOD DECK DETERIORATED, PITCH STEEP. IN FORNT OF UNIT 24 RAILING DECK DETERIORATED EDGE FILLED IN WITH PUTTY. DECK - WOOD BARRIER FENCE W/LATTACE DETERIORATED, DECK FLOOR DETERIORATED, SEPERATING, PEELING SPONGY. A/C HEAT PACK SMELL GAS, CALL S.W GAS, CALL S.W. GAS TO CHECK VENT CAPS CRUSHED DO NOT WORK AS INTENDED, ADDED ELECT CIRCUIT FROM A/C NO LIGHT FIXTURE, GAS LINE NEEDS BLOCKING AND SECURED ELECTRICAL SERVICE BOX TO CLOSE TO UNIT CANNOT WORK ON 10" POSSIBLE, INSTALLATION W/OUT DRAWING ON PERMITS |
|
| 08/15/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP BLD 1 C-13 BUILDING 1 EXTERIOR WEST END (2) LIGHT FIXTURES EXPOSED ELECTRICAL WEST END CONVENIENCE OUTLET NOT GFCI PROTECTED. WEST END 6 X 8 SUPPORT POST COMING AWAY FROM STRUCTURE WALL. WEST END WALKWAY FOR 2ND FLOOR HAS GAP. WEST END 6 X 8 SUPPORT POST DETERIORATED AT BASE LACKS PROPER SUPPORT. SOUTHSIDE BY APT 2 ADDED ELECTRICAL CIRCUIT FOR LIGHTING. ROMEX WIRING SPLICE AND WIRE NUTTED, HALLWAY BETWEEN APTS 1-2 EAST END, OVERHANG STARTING TO DETERIORATE, PLASTER CRUMBLING @ CORNER. WOOD BASKET FOR ELECT. DETERIORATING LACKS WEATHER PROTECTION. LIGHT FIXTURE BY ELEVATOR ROOM LOOSE FROM WALL, MISSING COVER 105 - EXTERIOR WOOD FOR DOOR JAMB SEPERATING, WINDOW FRAME BOWING 104. MOULDING ON JAMB TO SECURE DOOR, EAST OF DOOR CONVENIENCE OUTLET WEATHER BOX COVERS BROKEN NOT GFCI PROTECTED, LOOSE FROM WALL 103 WINDOW NEEDS RESEALING, DETERIORATED, SHOWS HOLE, 101 EXTERIOR LIGHT FIXTURE MISSING COVER. 2ND FLOOR STAIRWAY LIGHT FIXTURE MISSING COVER AND BULB. RAILING 34" @ LANDING. CEILING SHOWS DETERIORATION (METAL). 202 WINDOW NOT SEALED PROPERLY. OUTLET NOT GFCI PROTECTED. 204 - BOTTOM OF DOOR DETERIORATING. 205 - NEW DOOR NOT PAINTED. CEILING BY ELEVATOR PAINT PEELING METAL RUSTING. WEST END STAIRS GOING TO 3RD FLOOR LIGHT FIXTURE LOOSE @ WALL MISSING BULB AND COVER. WEST END 3RD FLOOR, LANDING COXAL WIRING HANGING @ WALL STAIR STEPS LOOSE @ WALL TO GET TO ROOF. LANDING - LIGHT FIXTURE MISSING COVER COXAL CABLE BOX COVER WILL NOT SECURE 305 DOOR NOT PAINTED 304 DOOR ROTTING - DETERIORATING 3RD FLOOR OUTLET NOT GFCI PROTECTED 303 DOOR NOT PAINTED - BROKEN 301 DOOR JAMB SEPERATING 3RD FLOOR EASTEND LIGHT FIXTURE ADDED, CIRUCIT ADDED EXPOSED ROMEX. LANDING WIRE MESH - SCREENING KICK OUT OF FRAME, WESTEND HOTWATER TANK ROOM, DRYWALL MISSING, ACCESS TO 101 TUB PLUMBING. EXPOSED ROMEX AT OPENING IN WALL, ADDED CONVENIENCE OUTLET, EXPOSED ELECTRICAL AT WATER HEATER TIMER, EXPOSED ELECTRICAL AT INTERMATIC TIMER, EXPOSED ELECTRICAL AT HOT WATER TANK. ALTERED PLUMBING LINE. WESTEND - 6 METERS, BACKING DETERIORATED, WEATHER HEAD FALLING SLIDING DOWNWARD, PUSHING EVERY THING ELSE DOWNWARD, PARTS NOT SECURED TO WALL. HEATER ROOM VENT FALLING 6 OF 7 GAS METERS NO GAS TREE NEEDS TRIMMING EAST END PANEL BOX. METER BOARD BACKING DETERIORATED. NO METERS ARE MARK OR IDENTIFIED. 101 LIGHT FIXUTRE IN REAR BROKEN LENS. EAST END OPEN JUNCTION BOX. EXPOSED ELECT, ADDED ROMEX LINE. |
|
| 08/15/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP BLD 2 C-13 BUILDING 2 - EXTERIOR WESTSIDE, NORTHEND OPEN AND EXPOSED COXIAL CABLE BOX. NORTHEND DECK SPLITTING. DETERIORATING FROM WATER SUPPORT POST SLIDING GLASS DOOR. 3 BOLTS RUSTED NOT HOLDING AS INTENDED SUPPORT POST BETWEEN #4 -5 DETERIORATED AT BOTTOM. SUPPORT POST UNIT 5 BOLTS COMING OUT, CONNECTIONS @ TOP DETERIORATING LIGHT FIXTURE HANGING FROM WALL #6. EAST SIDE - GAS LINE INSTALLED CALLED OFFICE, OPEN AND EXPOSED ELECT. WIRING CONDUIT INSTALLED, MISSING CAP. ELECTRIC METERS NOT LABELED, BACKER BOARD DETERIORATED, NEEDS PAINTING. EXPOSED ROMEX TO BLD LIGHT. EAST NORTH METERS BACKER BOARD STARTING TO DETERIORATE, NEEDS PAINT. 2ND FLOOR DECKING DETERIORATED, BROKEN BOARDS, RAILING ALONG 2ND FLOOR DECK 30". LIGHT FIXTURE LOOSE FROM WALL BETWEEN UNIT 25-26 BOARDS IN FRONT OF 26. RAILING NOT SECURED IN AREAS, DECKING WEAK IN FRONT OF 29-31 BOARDS SLIDING OUT OF POSITION BY 31. (3) SUPPORT BEAM, (14) DETERIORATED - TOP- BOTTOM, SUPORT BEAM (13) DETERIORATED. LIGHT FIXTURE (11) HANGING - EXPOSED ELECT. SUPPORT POST (11) NOT SECURED WESTSIDE. PUMP ROOM - ELECTRIC SERVICE PANEL MISSING DEAD PLATE, SHOWS DOUBLE LUGGING 2 BREAKERS, ADDED CIRCUITS, EXPOSED ROMEX, SEVERAL CONNECTIONS IN BOX, USING WHITE AS BLACK NOT MARKED, WIRE NUTS ON INTERIOR, JUNCTION BOX, OPEN AND EXPOSED ROMEX, CONNECTIONS, MISSING BOX COVER, TIMER OPEN AND EXPOSED ELECT. CONNECTIONS, NOT INSTALLED PROPERLY, CONVENIENCE OUTLET INSTALLED, GFCI NOT COVERED, ADDED CIRCUIT (CONDUIT). 6 ADDED CIRCUIT, ANOTHER OUTLET INSTALLED OPEN AND EXPOSED ROMEX, LACKS COVER PLATE, GAS LINE NOT SEUCRED, NEW HOT WATER TANK, PRV DOES NOT GO DOWN FAR ENOUGH, FLUE PIPE NOT SEALED AT JOINTS, SOUTHEND, ADDED CIRUIT OUTLET OPEN AND EXPOSED ROMEX, BOX CONNECTOR LOOSE. LAUNDRY ROOM- 3 PRONG OUTLETS, 1 SHOWS OPEN NEUTURAL, 1 SHOWS OPEN GROUND. |
|
| 08/13/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | 8/13/04, REVISITED SITE, TOOK PICTURES, MET WITH T.F.D. INSP. WAYNE CUMMINGS, STARTED EXTERIOR INSP. DONE BUILDING # 1, RUNS EAST AND WEST, FOUND SEVERAL ISSUES, LISTED BELOW. |
|
| 08/01/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 27 C-13 UNIT 27 - INTERIOR TC SEC 16-11 (C) ELECTRICAL SYSTEMS KITCHEN OUTLET BROKEN, DISP. OUT OF ORDER TC SEC 16-11 (E) PLUMBING SYSTEMS BATH COLD WATER SUPPLY HANDLE MISSING SHOWER AREA CAULKING MISSING IN AREAS. WALL HAS CRACK. TC SEC 16-11 (F) INTERIOR SURFACES AND FEATURES KITCHEN FLOOR WEAK OR SPONGY, KITCHEN VENT COVERED, BATH FLOOR WEAK AND SPONGY. |
|
| 08/01/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 201 C-13 UNIT 201 - INTERIOR TC SEC 16-11(C) ELECTRICAL SYSTEMS 3 PRONG L/R OUTLET SHOWS OPEN GROUND UNDER TEST, LITE SWITCH COVER BROKEN, DINING ROOM LITE EXPOSED ELECTRICAL WIRE CONNECTIONS. SPLICED TOGETHER, KITCHEN 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST. NOT GFCI PROTECTED UNDER SINK 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST, NO GFCI PROTECTED, DISP. OUT OF ORDER. BATH 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST BATH LITE FIXTURE HAS UNGROUNDED UNGFCI PROTECTED PLUG. TC SEC 16-11 (D) MECHANICAL SYSTEMS HEATER NEWER, DOULBE WALLED FLUE PIPE TAPED OVER. TC SEC 16-11 (E) PLUMBING SYSTEMS TOILET CONTINUOUSLY LEAKS. TC SEC 16-11 (F) INTERIOR SURFACES AND FEATURES KITCHEN FLOOR TILE MISSING IN AREAS (FRONT OF SINK) CHIPPED, CLOSET DOOR (HEATER) MISSING HANDLE. TC SEC 16-12 (A) EXTERIOR SURFACES/WEAHTER PROTECTION, DILAPIDATED STRUCTURES FRONT DOOR HAS HOLE, EXTERIOR, WEATHER STRIPPING MISSING IN AREAS, DOOR SWEEP BOTTOM COMING OFF. KITCHEN WINDOW BROKEN (TAPED UP) B/R WINDOW DOES NOT SIT IN WINDOW FRAME AS INTENDED DOES NOT OPEN, LEAK IN KITCHEN CEILING AND WALL (WESTSIDE). |
|
| 08/01/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 202 C-13 UNIT 202 - INTERIOR TC SEC 16-11 (A) FIRE SAFETY SMOKE DETECTORS OUT OF ORDER TC SEC 16-11 (C) ELECTRICAL SYSTEMS L/R WEST WALL OUTLET BROKEN, MISSING COVER, KITCHEN OUTLET 3 PRONG OUTLET NOT GFCI PROTECTED, READ OKAY, FRAYED WIRING IN FURNACE ROOM, EXPOSED ROMEX COMING FROM TOP GOING THROUGH FLOOR, B/R OUTELT BROKEN AND BURNT, BATHROOM OUTLET CAS USE, PAINTED OVER, NOT GFCI PROTECTED. TC SEC 16-11 (D) MECHANICAL SYSTEMS NEWER HEATER, STORING STUFF IN ROOM. TC SEC 16-11 (E) PLUMBING SYSTEM BATH FAUCET BROKEN COLD WATER HANDLE, SHOWER AREA CIELING HAD LEAK, COVERED W/WOOD. TUB AND SINK BOTH DRAIN SLOWLY. TC SEC 16-12 (A) EXTERIOR SURFACES/WEATHER PROTECTION, DILAPIDATED STRUCTURES FRONT DOOR WEATHER PROTECTION. |
|
| 08/01/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 203 C-13 UNIT 203 - INTERIOR TC SEC 16-4 PERMITS REQUIRED M.I. 4 DAYS AGO TC SEC 16-11 (A) FIRE SAFETY B/R WINDOW SCREWED IN CLOSED POSITION NO SMOKE DETECTOR TC SEC 16-11 (C) ELECTRICAL SYSTEMS L/R WEST WALL 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST LOOSE FOR WALL. TV CABLE BOX AND COVER, OUTLET EAST WALL BROKEN, OUTLET UNDER SINK 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST, NOT GFCI PROTECTED, KITCHEN OUTLET HAVE TO WIGGLE PLUG TO MAKE WORK. NOT GFCI PROTECTED. TC SEC 16-11 (D) MECHANICAL SYSTEMS FLUE PIPE WRAPPED W/ABESTO TAPE (FRAYING) COLD AIR RETURN BLOCKED, COMBUSTIBLE AIR. TC SEC 16-11 (E) PLUMBING SYSTEMS TOILET TANK LID LOOSE FROM TOILET, CAULKING BAD AROUND TUB AND FLOOR AND BATH SINK. MISC FRIG TO BIG TO SET IN OPENING. |
|
| 08/01/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 205 C-13 UNIT 205 - INTERIOR TC SEC 16-11 (C) ELECTRICAL SYSTEM L/R 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST BROKEN COVER PLATE, BOTH EAST AND WEST WALLS, KITCHEN 3 PRONG OUTLET WORN SHOWS OPEN GROUND UNDER TEST EXPOSED ELECTRICAL WIRING FURNACE ROOM, BATH LITE FIXTURES 3 PRONG OUTLET NOT GFCI PROTECTED, BATH 3 PRONG OULTET WORN SHOWS OPEN GROUND NOT GFCI PROTECTED, COVER BROKEN. TC SEC 16-11 (D) MECHANCIAL SYSTEMS USES HER OWN FRIG DUE TO ONE THAT CAME W/UNIT DOES NOT WORK VERY WELL DOES NTO KEEP FOOD COLD ENOUGH, STOVE MISSING SELECTOR KNOB, TEMP KNOB, FLUE PIPE JOINTS LACKING SEALANT, CAN NOT SHUT OFF HEATER GAS VALVE. TC SEC 16-11 (E) PLUMBING SYSTEMS PVC LINE ADDED FOR HOT WATER (KITCHEN FAUCET) LEAK UNDER KTICHEN SINK, TOILET DOES NOT OPERATE, RESIDENT USES BUCKET W/WATER TO FLUSH TC SEC 16-11 (F) INTERIOR SURFACES AND FEATURES KITCHEN FLOOR MISSING TILES IN AREAS, HOLE IN DRYWALL UNDER SINK, DRYWALL MISSING FURNACE ROOM DRYWALL MISSING UNDER BATH SINK, CARPET COMING UP BY BATH DOOR, B/R DOOR HAS HOLES. TC SEC 16-12 (A) EXTERIOR SURFACES/WEATHER PROTECTION, DILAPIDATED STRUCTURES WEATHER STRIPPING, FRONT DOOR, FRONT DOOR NOT PAINTED, BOTTOM OF DOOR SHOWS LITE. |
|
| 08/01/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 301 C-13 UNIT 301 TC SEC 16-11 (C) ELECTRICAL SYSTEM L/R BEHIND COUCH WEST WALL SHOWS OPEN GROUND UNDER TEST, KITCHEN EXHAUST FAN DOES NOT WORK. KITCHEN LITE HANGING FROM WALL, ALSO EXPOSED WIRING, BATH OUTLET SHOWS OPEN GROUND UNDER TEST. TC SEC 16-11 (D) MECHANICAL SYSTEMS COLD AIR RETURN NOT SECURED TO WALL. TC SEC 16-11 (E) PLUMBING SYSTEMS SHOWER HEAD CONTINUOUSLY LEAKS MISSING DIVERTER HANDLE, CAULKING SEPERATING AND CRACKING. TC SEC 16-11 (F) INTERIOR SURFACES AND FEATURES BATH FLOOR BASE MOULDING COMING AWAY FROM WALL. TC SEC 16-12 (A) EXTERIOR SURFACE/WEATHER PROTECTION, DILAPIDATED STRUCTURES |
|
| 08/01/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 301 C-13 UNIT 301 INTERIOR TC SEC 16-11 (C) ELECTRICAL SYSTEM L/R BEHIND COUCH WEST WALL SHOWS OPEN GROUND UNDER TEST, KTICEHN EXHAUST FAN DOES NOT WORK. KITCHEN LITE HANGING FROM WALL, ALSO EXPOSES WIRING, BATH OUTLET SHOWS OPEN GROUND UNDER TEST. TC SEC 16-11 (D) MECHANICAL SYSTEMS COLD AIR RETURN NOT SECURED TO WALL. TC SEC 16-11 (E) PLUMBING SYSTEMS SHOWER HEAD CONTINUOUSLY LEAKS, MSSING DIVERTER HANDLE, CAULKING SEPERATING AND CRACKING. TC SEC 16-11 (F) INTERIOR SURFACES AND FEATURES BATHFLOOR BASE MOULDING COMING AWAY FROM WALL. TC SEC 16-12 (A) EXTERIOR SURFACE/WEATHER PROTECTION, DILAPIDATED STRUCTURES FRONT DOOR WEATHER STRIPPING MISC STOVE FRONT R BURNER OUT OF ORDER. |
|
| 08/01/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 302 C-13 UNIT 302 - INTERIOR TC SEC 16-11 (A) FIRE SAFETY B/R WINDOW WILL NOT OPEN, NO SMOKE DETECTOR TC SEC 16-11 (C) ELECTRICAL SYSTEMS L/R OUTLET EAST WALL SHOWS OPEN GROUND UNDER TEST, KITCHEN OULTLET SHOWS OPEN GROUND UNDER TEST NOT GFCI PROTECTED, DISP OUTLET SHOWS OPEN GROUND UNDER TEST NOT GFCI PROTECTED. EXPOSE ROMEX LINE COMING FROM TOP GOING THROUGH FLOOR, BATH 3 PRONG OUTLET PAINTED OVER CANNOT USE NOT GFCI PROTECTED. TC SEC 16-11 (D) MECHANICAL SYSTEMS KITCHEN EXHAUST FAN OUT OF ORDER. NEW FURNACE, NEW FLUE PIPE, HEATER ROOM BEING USED FOR STORAGE ABESTO TAPE AROUND FLUE PIPE JOINTS, DETERIORATING IT. THERMO STAT WILL NOT OPERATE TO TEMP. TC SEC 16-11 (E) PLUMBING SYSTEMS TOILET ANGLE STOP MISSING HANDLE, SHOWER WALL AND CEILING NEEDS CAULKING. TC SEC 16-11 (F) INTERIOR SURFACES AND FEATURES HALLWAY DRYWALL HAS CRACKS. TC SEC 16-12 (A) EXTERIOR SURFACES/WEATHER PROTECTION, DILAPIDATED STRUCTURES FRONT DOOR WEATHER PROECTION, INTERIOR DOOR SWEEP FALLING OFF, L/R WINDOW BOTTOM R DOES NOT SET IN FRAME PROPERLY HAS GAP. MISC FRIG DOORS BACKWARDS. |
|
| 08/01/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 304 C-13 UNIT 304 - INTERIOR TC SEC 16-11 (C) ELECTRICAL SYSTEMS L/R 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST, WEST WALL PLUG BROKEN KITCHEN WALL SOUTH, 3 PRONG OUTELT SHOW OPEN GROUND UNDER TEST, KTICHEN OUTLET 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST (WORN), DISP OUT OF ORDER. 3 PRONG PLUG SHOWS OPEN GROUND. BATH 3 PRONG OUTLET PAINTED OVER CANNOT INSTALL TEST PLUG, NOW GFCI PROTECTED OUTLET ALSO AT LITE FIXTURE. TC SEC 16-11 (D) MECHANICAL SYSTEMS FRIG FF DOOR GASKET SPLIT FLUE PIPE JOINTS NEEDS RESEALING, (ABESTOS TAPE) HEATER GAS VALVE HAS BEEN CHANGED. TC SEC 16-11 (E) PLUMBING SYSTEMS COLD WATER VALVE LETS VERY LITTLE COLD WATER PASS, BATH FAUCET NO HOT WATER, COLD LEAKS UNDER SINK WHEN USED, FLOOR COVERED W/WATER TOILET TANK LID MISSING. TC SEC 16-11 (F) INTERIOR SURACES AND FEATURES HOLE IN DRYWALL, ACCESS PANEL HEATER ROOM, DOOR HANDLE MISSING B/R DOOR. TC SEC 16-12 (A) EXTERIOR SURFACES/WEATHER PROTECTION, DILAPIDATED STRUCTURES BOTTOM OF FRONT DOOR DETERIORATED SHOWS LITE AT BOTTOM. |
|
| 08/01/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 305 C-13 UNIT 305 VACANT UNIT |
|
| 07/29/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 29 C-13 UNIT 29 - INTERIOR TC SEC 16-11 (A) FIRE SAFETY NO SMOKE DETECTOR, BEDROOM WINDOW BLOCKED BY DRESSER AND MIRROR - MASTER. 2ND FLOOR FUSE PANEL BLOCKED IN. TC SEC 16-11 (C) ELECTRICAL SYSTEMS BATH FIXTURE MISSING COVER, EXPOSED ROMEX WIRING IN HOT WATER ROOM, COMBUSTABLES BEING STORED. TC SEC 16-11 (D) MECHANICAL SYSTEMS KITCHEN EXHAUST FAN OUT OF ORDER. TC SEC 16-11 (F) INTERIOR SURFACES AND FEATURES KITCHEN FLOOR SPONGY AND WEAK ADDITIONAL SUB FLOOR, ADDED STILL WEAK, COLD AIR RETURN NOT SECURED TO WALL, BATH CEILING PAINT PEELING AND BUBBLING. TC SEC 16-12 (A) EXTERIOR SURFACES/WEATHER PROTECTION, DILAPIDATED STRUCTURES BOTTOM OF DOOR SHOWS LIGHT. MISC FRIG. DOES NOT OPERATE AS INTENDED, HAS TO PUT THINGS IN FREEZER TO KEEP COLD, BOTTOM NOT VERY COLD. |
|
| 07/29/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 30 C-13 UNIT 30 - VACANT TC SEC 16-11 (E) PLUMBING SYSTEMS NEW PRV LINE |
|
| 07/29/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 31 C-13 UNIT 31 - VACANT UNIT SEC TC 16-11 (C) ELECTRICAL SYSTEMS EXPOSED ELECTRICAL ROMEX IN HOT WATER TANK STORAGE ROOM. TC SEC 16-11 (D) MECHANICAL SYSTEMS HOT WATER TANK FLUE PIPE LACKS SEALANT AROUND JOINTS. TC SEC 16-11 (E) PLUMBING SYSTEMS NEWER HOT WATER TANK, NO COLD WATER SHUT OFF. |
|
| 07/28/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 103 C-13 UNIT 103 - INTERIOR INSPECTION TC SEC 16-11 (A) FIRE SAFETY SMOKE DETECTOR OUT OF ORDER TC SEC 16-11 (C) ELECTRICAL SYSTEMS L/R NORTHWALL 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST. DISP. SHOWS EXPOSED WIRING, BATH 3 PRONG OUTLET NOT GFCI PROTECTED, READ OKAY. TC SEC 16-11 (D) MECHANICAL SYSTEMS HEATER NEWER, FLUE PIPE NEWER. TC SEC 16-11 (E) PLUMBING SYSTEMS KITCHEN CLOSET - PVC LINE, ADDED TO SUPPLY HOTWATER TO KITCHEN FAUCET, BATH FAUCET LOOSE FROM SINK, TOILET TANK LOOSE FROM TOILET. SHOWER ENCLOSED HAS HOLE IN WALL, COVERED BY TAPE, BATH CEILING. TC SEC 16-11 (E) INTERIOR SURFACES AND FEATURES HOLE IN DRYWALL KITCHEN CLOSET. HOLE UNDER BATH VANITY, DRYWALL, BATH CIELING SHOWS EVIDENCE OF LEAK FROM ABOVE. SEC TC 16-12 (A) EXTERIOR SURFACES/WEATHER PROTECTION, DILAPIDATED STRUCTURES FRONT DOOR WEATHER STRIPPING. |
|
| 07/28/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 104 C-13 UNIT 104 - INTERIOR TC SEC 16-11 (A) FIRE SAFETY SMOKE DECTECTOR OUT OF ORDER. B/R WINDOW SCREWED IN CLOSED POSITION. TC SEC 16-11 (C) ELECTRICAL SYSTEMS L/R OUTLET WEST WALL 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST, COVER BROKEN, KITHCEN OUTLET NOT GFCI PROTECTED, EXPOSED ELECTRICAL WIRING AT DISP. BATH NOT GFCI PROTECTED, 3 PRONG OUTLET READ OKAY, BATH LIGHT FIXTURE HAS PLUG. TC SEC 16-11 (D) MECHANICAL SYSTEMS HEATER BEEN INSTALLED. TC SEC 16-11 (E) PLUMBING SYSTEMS PVC LINE HAS BEEN ADDED FOR KITCHEN FAUCET HOT WATER, ACCESS PANEL FOR 105 INSIDE. 104 CLOSET, PVC LINE ADDED FOR HOT WATER TO BATH FAUCET TOILET DOES NOT FLUSH AS INTENDED TILES IN SHOWER AREA, GROUT MISSING NEEDS RESEALING. TC SEC 16-11 (F) INTERIOR SURFACES AND FEATURES CLOSET WEST SIDE KITCHEN FLOOR MISSING, DRYWALL MISSING, DRYWALL MISSING FROM UNDER SINK. TC SEC 16-12 (A) EXTERIOR SURFACES/WEATHER PROTECTION, DILAPIDATED STRUCTURES FRONT DOOR WEATHER STRIPPING MISC FRIG FF DOOR HANDLE MISSING. TC SEC 16-11 (A) FIRE SAFETY SMOKE DETECTOR OUT OF ORDER. B/R WINDOW SCREWED IN CLOSED POSITION. TC SEC 16-11 (C) ELECTRICAL SYSTEMS L/R OUTLET WEST WALL 3 PRONG OUTLET, SHOWS OPEN GROUND UNDER TEST, COVER, BROKEN, KITCHEN OUTLET NO GFCI PROTECTED EXPOSED ELECTRICAL WIRING AT DISPOSAL. BATH NOT GFCI PROTECTED, 3 PRONG OUTLET READS OKAY, BATH LIGHT FIXTURE HAS PLUG. |
|
| 07/28/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 105 C-13 UNIT 105 - INTERIOR TC SEC 16-11 (A) FIRE SAFETY SMOKE DETECTOR WRONG PLACE ON INSIDE OF KITCHEN WALL. DOES NOT WORK, 2ND SMOKE DETECTOR ALSO OUT OF ORDER. TC SEC 16-11 (C) ELECTRICAL SYSTEMS LIGHT SWITCH FOR LIGHT OVER SINK DOES NOT OPERATE AS INTENDED. (WEAK), 3 PRONG OUTLET SHOWS OPEN GROUND UNDER TEST, PAINT COVERING GROUND HOLE ON TOP PART OF PLUG HAS OUTLET INSTALLED UNDER SINK, NO COVER AND EXPOSED WIRING, LIGHT SWITCH OR LIGHT FIXTURE FOR L/R DOES NOT OPERATE, BATH HAS 3 PRONG OUTLET NOT GFCI PROTECTED, HAVE TO WIGGLE PLUG TO MAKE IT OPERATE NORMALLY, OTHERWISE SHOWS OPEN GROUND UNDER TEST. TC SEC 16-11 (E) PLUMBING SYSTEMS PVC LINE THAT IS UNDER BATH VANITY GOES TO KITCHEN FIXTURE, HOT WATER LINE (INSTALLED) BATH SHOWER AREA TILES BROKEN, MISSING GROUT AND CAULKING. FAUCET IN KITCHEN LEAKS. TC SEC 16-11 (F) INTERIOR SURFACES AND FEATURES DRYWALL MISSING FROM UNDER SINK, DRYWALL IN BATH WEST WALL AT FLOOR DETERIORATED. TC SEC 16-12 (A) EXTERIOR SURFACES/WEATHER PROTECTION, DILAPIDATED STRUCTURES FRONT DOOR WEATHER STRIPPING, LEFT SIDE. |
|
| 07/27/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | 7/27/04, VISITED SITE, MET WITH INSP. WAYNE CUMMINGS FROM T.F.D. ON SITE, STARTED INTERIOR INSPECTIONS OF UNITS, 3,4,5,6,7,9,10,11,12,13,14,15,23,32. DONE ON 7/27/04 UNIT 3: DISPOSAL DOES NOT WORK, HAS EXPOSED ELECTRICAL WIRING. KITCHEN CONVENIENCE OUTLET NOT GFCI PROTECTED. DINING ROOM LIGHT FIXTURE MISSING COVER. BATH EXHAUST FAN DOES NOT OPERATE. BATH ROOM LIGHT FIXTURE HAS 3 PRONG CONVENIENCE OUTLET NOT GFCI PROTECTED. NEWER HOT WATER TANK INSTALLED, PRESSURE RELIEF VALVE NOT DIRECTED TO EXTERIOR OF STRUCTURE. FLUE PIPE INSTALLED AT A 90 DEGREE ANGLE. EMERGENCY WATER SHUT OFF IS NOT ACCESSABLE, SITS APPOX. 6' IN HEIGHT AND BEHIND TANK, GAS SUPPLY VALVE NOT A.G.A. APPROVED. EXPOSED ROMEX WIRING AT BOTTOM OF STRUCTURE. HOT WATER ANGLE STOP MISSING HANDLE. SHOWER WALL COVERING SHORT, NOT AT 70 INCHES. FRONT DOOR WEATHER STRIPPING DETERIORATED AND OR MISSING IN AREAS. REFRIGERATOR DOOR HANDLE BROKEN. UNIT 4: SMOKE DETECTOR BROKEN DOES NOT OPERATE. B/R WINDOW SCREWED CLOSED. WINDOW FRAME NEEDS RESEALING. EXPOSED ELECTRICAL WIRING AT DISPOSAL. 3 PRONG CONVENIENCE OUTLET IN KITCHEN NOT GFCI PROTECTED. B/R MISSING LIGHT FIXTURE COVER. BATH ROOM LIGHT FIXTURE HAS CONVENIENCE OUTLET PLUG NOT GFCI PROTECTED. BATH TUB WATER FIXTURE CONTINOUSLY LEAKS. NEW HOT WATER TANK, PRESSURE RELIEF VALVE NOT DIRECTED TO EXTERIOR OF STRUCTURE, FLUE PIPE AT 90 DEGREE ANGLE, GAS SUPPLY VALVE NOT A.G.A. APPROVED. DRYWALL IN BATH ROOM DETERIORATED BY WATER AT FLOOR. COOK STOVE LIGHT STAY IN THE ON POSITION. UNIT 5: SMOKE DETECTOR NOT OPERATING. HOT WATER TANK NEWER, NO EMERGENCY WATER SHUT OFF, PRESSURE RELIEF VALVE NOT DIRECTED TO EXTERIOR OF STRUCTURE. HOT WATER TEMPERATURE CONTROL KNOB MISSING. GAS SUPPLY VALVE NOT A.G.A. APPROVED. FLUE PIPE NOT PROPERLY INSTALLED, 90 DEGREE ANGLE. B/R HAS BROKEN WINDOW. UNIT 6: SMOKE DETECTOR NOT OPERATING. BATH ROOM LIGHT FIXTURE HAS 3 PRONG PLUG CONVENIENCE OUTLET NOT GFCI PROTECTED, FIXTURE LOOSE FROM WALL. EXHAUST FAN MISSING FROM VENT TUBE, ONLY HAS OPEN SPACE. TOILET LOOSE FROM FLOOR. TOILET TANK LOOSE FROM TOILET. HOT WATER FAUCET HANDLE DOES NOT OPERATE. TOILET KEEPS RUNNING CONTINOUSLY. CARPET COMMING UP AT CONNECTION AT BATHROOM DOOR. WHERE DRYWALL MEETS CEILING HAS GAPS AND CRACKS. B/R WINDOW SCREWED CLOSED CAN NOT OPEN. B/R WINDOW BROKEN. FRONT DOOR WEATHER STRIPPING DETERIORATED AND MISSING IN AREAS. SLIDING GLASS DOOR HANDLE IS BROKEN, DOOR WILL NOT OPEN. REFRIGERATOR F.F. HANDLE BROKEN. UNIT 7: VACANT UNIT:: HOT WATER TANK NEWER, FLUE PIPE INSTALLED AT 90 DEGREE ANGLE, GATE VALVE CONTINOUSLY LEAKS, FLOOR DETERIORATING FROM WATER LEAK, PRESSURE RELIEF VALVE DRAIN LINE NOT DIRECTED TO EXTERIOR. UNIT 9: SMOKE DETECTOR MISSING. HOT WATER TANK EMERGENCY COLD WATER SHUT OFF MISSING HANDLE. PRESSURE RELIEF VALVE DRAIN LINE NOT DIRECTED TO EXTERIOR OF STRUCTURE. NEWER TANK INSTALLED 3/93 UNIT 10: UNIT 11: UPON ARRIVAL TO THIS UNIT FOUND EXTENSION COMMING OUT OF FRONT DOOR GOING INTO UNIT NEXT DOOR SLIDING GLASS DOOR, UNIT 12, UNIT 11 WAS SUPPLYING POWER TO UNIT 12 VIA EXTENSION CORD. EXPLAINED TO RESIDENT IN UNIT 11 THIS WAS ILLEGAL, HE STATED HE STOPED DUE TO HIS ELECTRIC BILL WENT SKY HIGH, RESIDENT REMOVED CORD FROM UNIT LAID IT IN FRONT OF UNIT 12 SLIDING GLASS DOOR, FINISHED INSP. ON UNIT 11: FRONT DOOR HAS ADDITIONAL LOCKING MECHANISM INSTALLED ON DOOR. SMOKE DETECTOR DOES NOT OPERATE. N/W BEDROOM WINDOW HAS BEEN SECURED BY SCREW IN THE CLOSED POSITION. N/W BEDROOM HAS LOCKING DOOR HANDLE FROM OUTSIDE, CAN NOT LEAVE ROOM FROM INSIDE IF DOOR IS LOCKED, SAME DOOR HAS HASP ON EXTERIOR OF DOOR IF LOCKED CAN NOT GET OUT OF ROOM. BATHROOM EXHAUST FAN DOES NOT OPERATE. BATHROOM CEILING TILES DETERIORATED FROM WATER LEAK. BATH TUB DRAINS SLOWLY. CAULKING IN SHOWER AREA DETERIORATING AND CRACKING. REFRIGERATOR MISSING F.F., FREEZER DOOR HANDLES. REFRIGERATOR F.F. DOOR GASKET BAD. HOT WATER TANK AREA HAS EXPOSED ELECTRICAL WIRING, WIRING HAS BEEN SPLICED TOGETHER. HOT WATER TANK FLOORING DETERIORATED FROM WATER LEAK. TANK LISTING AND LEANING. NO COLD WATER EMGERENCY SHUT OFF INSTALLED ON TANK. NO PRESSURE RELIEF VALVE DRAIN LINE INSTALLED ON HOT WATER TANK. UNIT 12: NO ONE AT UNIT AT THIS TIME. DONE NOTICE OF EMERGENCY ABATEMENT AND ORDER TO VACATE DUE TO NO ELECTRIC, AND HAZARDOUSLY SUPPLYING ELECTRICAL POWER THROUGH EXTENSION CORD. T.E.P. DISCONTINUED ELECTRICAL POWER ON 7/9, POSTED UNIT 7/27. HAVE NOT DONE INTERIOR INSP. AS OF YET. UNIT 13: VACANT UNIT AT THIS TIME: HOT WATER TANK AREA SHOWS, HOT WATER TANK PRESSURE RELIEF VALVE NOT DIRECTED TO EXTERIOR OF STRUCTURE, HOT WATER TANK AREA FLOORING DETERIORATED FROM WATER LEAK. UNIT 14: NO SMOKE DETECTOR. NEW HOT WATER TANK. FLUE PIPE NEEDS RESEALING AT JOINTS, FLUE PIPE IS INSTALLED AT 90 DEGREE ANGLE. BEDROOM WINDOW SECURED BY SCREW IN CLOSED POSITION. UNIT 15: KITCHEN HAS 2,-3 PRONG OUTLETS INSTALLED NOT GFCI PROTECTED. L/R LIGHT SWITCH CONTROLS ALL ELECTRIC POWER TO 3 SEPERATE CONVENIENCE OUTLETS IN L/R. BATHROOM LIGHT FIXTURE HAS CONVENIENCE OUTLET INSTALLED NOT GFCI PROTECTED. KITCHEN HAS EXPOSED GAS LINE BY STOVE, GOES FROM CEILING DOWN TO STOVE. BATHROOM SINK LEAKS UNDERNEITH IN VANITY. TOILET DOES NOT FLUSH AS INTENDED. APPEARS WATER LINE IN BEDROOM CLOSET HAS BEEN ADDED. DRYWALL IN KITCHEN CEILING SAGGING DUE TO CURRENT WATER LEAK. HOLE IN BEDROOM WALL, DRYWALL. BEDROOM WINDOW DOES NOT OPERATE AS INTENDED. EXPOSED DUCT WORK IN BEDROOM CLOSET, NOT PROPERLY SEALED, ADDED SHEET METAL OVER OPENING WHERE FURNANCE USED TO CONNECT, FURNANCE HAS BEEN REMOVED, ANOTHER SOURCE OF HEAT HAS BEEN INSTALLED. APT APPEARS TO HAVE BEEN STORE ROOM OR SOMETHING ON THIS LINE AND HAS BEEN CONVERTED IN RENTAL. UNIT 23: BEDROOM WINDOW SECURED IN THE CLOSED POSITION BY A SCREW. KITCHEN HAS 3 PRONG OUTLETS NOT GFCI PROTECTED. HOT WATER TANK COLD WATER EMERGENCY SHUT OFF VALVE MISSING HANDLE. PRESSURE RELIEF VALVE DRAIN LINE NOT DIRECTED TO EXTERIOR OF STRUCTURE. FLUE PIPE JOINT CONNECTION NEEDS TO BE RESEALED. LIVING ROOM FLOOR SPONGY, DETERIORATING IN AREAS. UNIT 32: VACANT UNIT: HOT WATERTANK STORAGE ROOM CEILING DRYWALL FALLING OFF. COLD WATER SUPPLY LACKS EMERGENCY SHUT OFF. NEWER HOT WATER TANK (1990) HOT WATER TANK STORAGE ROOM FLOOR DETERIORATING FROM WATER LEAK. PRESSURE RELIEF NOT DIRECTED TO EXTERIOR OF STRUCTURE. INTERIOR INSP. DONE ON 7/29/04 UNIT 103: SMOKE DETECTOR DOES NOT OPERATE. LIVINGROOM NORTHWEST WALL HAS 3 PRONG OUTLET INSTALLED, SHOWS OPEN GROUND UNDER TEST. DISPOSAL HAS EXPOSED WIRING AND SPL;ICED WIRING. BATHROOM HAS 3 PRONG OUTLET, NOT GFCI PROTECTED. HEATER NEW INSTALLATION. FLUE PIPING NEW INSTALLATION. KITCHEN CLOSET SHOWS WHERE ALTERATION HAS BEEN MADE TO WATER SUPPLY SYSTEM, PVC HAS BEEN ADDED TO HOT WATER SYSTEM TO SUPPLY HOT WATER TO KITCHEN AND BATHROOM. BATHROOM FAUCET LOOSE FROM VANITY. TOILET TANK LOOSE FROM TOILET. FIBERGLASS SHOWER ENCLOSER HAS HOLE IN IT, SECURED BY TAPE. BATHROOM CEILING DRYWALL AND PAINT DETERIORATING DUE TO WATER LEAK. DRYWALL MISSING FROM UNDER BATHROOM VANITY AND KITCHEN CABINET. FRONT ENTRY DOOR WEATHER STRIPPING DETERIORATED MISSING IN AREAS. UNIT 104: SMOKE DETECTOR DOES NOT OPERATE. BEDROOM WINDOW SECURED IN THE CLOSED POSITION WITH SCREW. LIVINGROOM CONVENIENCE OUTLET SHOWS OPEN GROUND UNDER TEST, IS BROKEN, MISSING COVER PLATE. KITCHEN CONVENIENCE OUTLET NOT GFCI PROTECTED. EXPOSED WIRING AT DISPOSAL. BATHROOM CONVENIENCE OUTLET NOT GFCI PROTECTED. BATHROOM LIGHT FIXTURE HAS 3 PRONG CONVENIENCE OUTLET NOT GFCI PROTECTED. NEWER HEATER INSTALLED. ALTERATIONS TO WATER SUPPLY SYSTEM BY REPLACING ORIGINAL HOT WATER LINES WITH PVC LINES TO BOTH KITCHEN HOT WATER AND BATHROOM HOT WATER. TOILET DOES FLUSH PROPERLY. 3 PRONG CONVENIENCE OUTLET UNDER KITCHEN SINK NOT GFCI PROTECTED. FLUE PIPE VENTING HAS OLD ASBESTOS TAPE FOR SEALING JOINTS AND IS COMMING APART NEEDS INCAPSULATED. KITCHEN CLOSET, HEATER ROOM HAS SHOWS EXPOSED ELECTRICAL WIRING ALSO WHERE EXTERIOR COATING HAS DETERIORATED. KITCHEN EXHAUST FAN DOES NOT OPERATE. CONVENIENCE OUTLET IN DINING ROOM SHOWS BURN MARKS. CONVENIENCE OUTLETS HAS BEEN PAINTED OVER AND CAN NOT USE AS INTENDED. BATHROOM SINK COLD WATER SUPPLY HANDLE MISSING. BATHROOM CEILING SHOWS START OF REPAIR FROM WATER LEAK HAS NOT BEEN COMPLETED DUE TO NOT PROPERLY SEALED TO PROTECT FROM ABSORBENTS, AND TO PROTECT STRUCTURE. UNIT 105: SMOKE DETECTOR LOCATED IN WRONG LOCATION, ON INSIDE OF KITCHEN WALL, ALSO DOES NOT OPERATE. LIGHT SWITCH FOR LIGHT OVER KITCHEN SINK DOES NOT OPERATE. KITCHEN HAS 3 PRONG CONVENIENCE OUTLETS SHOWS OPEN GROUND UNDER TEST. CONVENIENCE OUTLETS PAINTED OVER, PAINT HAS COVER GROUND PLUG PORT ON CONVENIENCE OUTLET. CONVENIENCE OUTLET HAS BEEN INSTALLED UNDER KITCHEN SINK HAS NO COVER, AND HAS EXPOSED ELECTRICAL WIRING. LIGHT SWITCH OR LIGHT FIXTURE FFOR LIVING ROOM DOES NOT OPERATE. BATH HAS 3 PRONG OUTLET NOT GFCI PROTECTED, HAVE TO WIGGLE PLUG TO MAKE IT WORK. ALTERATIONS HAS BEEN MADE TO WATER SUPPLY SYSTEM, PVC WATER LINE HAS BEEN ADDED TO SUPPLY HOT WATER TO KITCHEN AND BATH PLUMBING FIXTURES. BATH SHOWER AREA HAS BROKEN TILES ON WALL, MISSING GROUT AND CAULKING IN AREAS. KITCHEN PLUMBING FIXTURE CONTINOUSLY LEAKS. DRYWALL MISSING FROM UNDER SINK. DRYWALL IN BATH, WEST WALL AT BOTTOM DETERIORATED FROM WATER LEAKS. FRONT DOOR LACKING WEATHER STRIPPING IN AREAS. UNIT 202: SMOKE DETECTOR DOES NOT OPERATE. LIVINGROOM WEST WALL CONVENIENCE OUTLET BROKEN, AND MISSING COVER PLATE. KITCHEN CONVENIENCE OUTLET NOT GFCI PROTECTED. FURNANCE ROOM HAS FRAYED WIRING. EXPOSED ELECTRICAL ROMEX COMMING FROM TOP GOING THROUGH FLOOR. BEDROOM HAS BROKEN CONVENIENCE OUTLET, ALSO SHOWS WHERE HAS BURNT. BATHROOM CONVENIENCE OUTLET HAS BEEN PAINTED OVER AND HOLES ARE FILLED WITH PAINT, ALSO NOT GFCI PROTECTED. HEATER HAS BEEN REPLACED. STORING COMBUSTABLES IN HEATER ROOM. BATHROOM FAUCET HAS BROKEN COLD WATER HANDLE, SHOWER AREA CEILING SHOWS DETERIORATION FROM WATER LEAK. HAS BEEN RECOVERED WITH WOOD. BOTH SHOWER AREA TUB AND BATH SINK DRAINS SLOWLY. FRONT DOOR WEATHER STRIPPING MISSING IN AREAS, DOOR DOES NOT SEAL PROPERLY. UNIT 203: BEDROOM WINDOW SECURED IN THE CLOSED POSITION BY SCREW. DWELLING LACKS SMOKE DETECTOR. LIVINGROOM WEST WALL 3 PRONG CONVENIENCE OUTLET SHOWS OPEN GROUND UNDER TEST, ALSO LOOSE FROM WALL. CONVENIENCE OUTLET EAST WALL BROKEN. CONVENIENCE OUTLET UNDER KITCHEN SINK SHOWS OPEN GROUND UNDER TEST, NOT GFCI PROTECTED. KITCHEN CONVENIENCE OUTLET AT COUNTER HAVE TO WIGGLE TO MAKE CONTACT, NOT GFCI PROTECTED. FLUE PIPE IN HEATER ROOM HAS ABESTO TAPE AND IS FRAYING OFF. COMBUSTABLE AIR VENT BLOCKED. TOILET TANK LOOSE AT TOILET. CAULKING AROUND TUB, SHOWER AREA, BATH SINK, AND FLOORING DETERIORATED. REFRIGERATOR INSTALLED IN UNIT TO BIG FOR OPENING, SETS IN MIDDLE OF FLOOR IN KITCHEN. UNIT 301: DWELLING LACKS SMOKE DETECTOR. LIVINGROOM WEST WALL 3 PRONG CONVENIENCE OUTLET SHOWS OPEN GROUND UNDER TEST. KITCHEN EXHAUST FAN DOES NOT OPERATE. KITCHEN LIGHT FIXTURE HANGING FROM WALL, ALSO HAS EXPOSED ELECTRICAL WIRING. BATHROOM CONVENIENCE OUTLET SHOWS OPEN GROUND UNDER TEST. COLD AIR RETURN VENT COVER NOT SECURED TO WALL. SHOWER HEAD CONTILOUSLY LEAKS. TUB, SHOWER AREA MISSING SHOWER DIVERTER HANDLE. CAULKING SEPERATING AND DETERIORATING. BATHROOM FLOOR BASE MOULDING COMMING AWAY FROM WALL. FRONT DOOR WEATHER STRIPPING MISSING AND OR DETERIORATED IN AREAS, DOOR WILL NOT SEAL PROPERLY. COOK STOVE RIGHT FRONT BURNER DOES NOT OPERATE AS INTENDED. UNIT 302: BEDROOM WINDOW WILL NOT OPEN AS INTENDED. DWELLING LACKS SMOKE DETECTOR. LIVINGROOM CONVENIENCE OUTLET EAST WALL SHOWS OPEN GROUND UNDER TEST. KITCHEN CONVENIENCE OUTLET SHOWS OPEN GROUND UNDER TEST, NOT GFCI PROTECTED. HEATER ROOM HAS EXPOSED ELECTRICAL ROMEX, COMMING FROM TOP OF CEILING THROUGH BOTTOM OF FLOOR. BATHROOM 3 PRONG CONVENIENCE OUTLET HAS BEEN PAINTED OVER AND CAN NOT USE, NOT GFCI PROTECTED. KITCHEN EXHAUST FAN DOES NOT OPERATE. NEW HEATER INSTALLED. NEW FLUE PIPE INSTALLED. HEATER ROOM BEING USED TO STORE COMBUSTABLES. ABESTO TAPE AROUND FLUE PIPE JOINTS COMMING APART AND DETERIORATING. TOILET ANGLE STOP MISSING HANDDLE. SHOWER WALL AND CEILING NEEDS TO BE PROPERLY SEALED. FRONT DOOR WEATHER STRIPPING DETERIORATED AND MISSING IN AREAS. INTERIOR DOOR SWEEP FALLING OFF. LIVINGROOMWINDOW, BOTTOM RIGHT DOES NOT SIT IN FRAME PROPERLY LEAVES A GAP. REFRIGERATOR DOORS ARE ON WRONG SIDE HARD TO OPEN. UNIT 305: VACANT UNIT. UNIT 25: FRONT DOOR MISSING THROW LATCH TO HANDLE DOOR WILL NOT STAY CLOSED, USING HASP TO HOLD DOOR IN CLOSED POSITION. ELECTRICAL JUNCTION BOX UNDER KITCHEN SINK NOT SECURED TO WALL. BATHROOM LIGHT HAS CONVENIENCE OUTLET INSTALLED NOT GFCI PROTECTED. SHOWER, TUB AREA PLUMBING FIXTURE LEAKS CONTINOUSLY. HOT WATER TANK SHOWS EVIDENCE OF BACK LASH FROM FLAME WHEN IGNIGHTING, FRONT OF HEATER BURNT. COMBUSTABILES BEING STORED IN HOT WATER TANK ROOM. HOT WATER TANK LACKS PRESSURE RELIEF VALVE DRAIN LINE. UNIT 26: SMOKE DETECTOR DOES NOT OPERATE. RESIDENT MADE COMPLAINT OF WHEN IT RAINS THE A/C TURNS OFF AND COME BACK ON AFTER IT DRIES OUT. TOILET DOES NOT FLUSH AS INTENDED, NOT ENOUGH WATER FLOW. HOT WATER TANK MISSING PRESSURE RELIEF VALVE DRAIN LINE. COMBUSTABLE MATERIAL BEING STORED IN HOT WATER TANK ROOM. POOL AREA: BARRIER FENCE SUPPORT POST RUSTED THROUGH IN AREAS, AT BOTTOM. EAST SIDE BARRIER FENCE HAS LOST STRENGHT AND STABILITY DUE TO BROKEN SUPPORT POST AND CORNER BRACKETS. NORTH SIDE BARRIER FENCE NOT PROPERLY SECURED. SOUTHEAST CORNER BARRIER FENCING GOING UP TO SECOND FLOOR AND LANDING IS ONLY 3' IN HEIGHT. HAS ADDED ELECTRICAL CIRCUITS INTO POOL AREA. |
|
| 07/27/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | INITIAL INSP UNIT 32 C-13 UNIT 32 - VACANT UNIT TC SEC 16-11 (E) PLUMBING SYSTEM EMERGENCY SHUT OFF HOT WATER TANK NO COLD WATER PRV DRAIN LINE NOT DIRECTED TO EXTERIOR, INSTALLED IN 11/90. TC SEC 16-12 (A) EXTERIOR SURFACES/WEATHER PROTECTION, DILAPIDATED STRUCTURES STORAGE ROOM CIELING DRYWALL FALLING. |
|
| 07/22/2004 | INSP - INITIAL CODE ENFORCMENT | Correction Required | 7/20/04, RECIEVED E-MAIL FROM CECI CONCERNING CHATEAU APTS. CALLED WAYNE CUMMINGS, T.F.D. AT THIS TIME WE SET UP INSP. DATE, 7/27/04, VISITED SITE ON 7/22/04, TO TALK WITH PROPERTY MANAGER ABOUT INSP. PROCESS, SABER, NO MANAGER ON SITE, TALKED WITH MAINTENANCE WHO STATED THAT I WOULD NEED TO TALK WITH MR. HARVEY EVENCHIK, I WENT TO 1402 N ALVERNON, CHATEAU APT. OFFICE, TALKED WITH MR EVENCHIK AND EXPLAINED DUE TO COMPLAINTS AND HISTORY OF ISSUES WILL BE DOING SABER INSP. MR. EVENCHIK AGREED AND I GAVE HIM SEVERAL NOTICE OF INSPECTION, MR EVENCHIK ASK IF EVERY UNIT IS TO GET ONE AND I STATED YES SO EVERY ONE IS AWARE WE WILL BE THERE ON THIS DATE, WE WILL BE DOING ALL INTERIORS, HE STATED OK, AT THIS TIME MR EVENCHIK IS AWARE OF INSPECTION DATE, AND OF ALL UNITS. WHEN I CAME BACK TO OFFICE HAD A VOICE MAIL, VOICE MAIL FROM MR EVENCHIK, ASKING ME TO RETURN HIS CALL, I DID THIS, MR EVENCHIK STATED THAT HE IS DONATING PROPERTY AS A GIFT, IS DONATING TO FAMILY HOUSING RESOURCES, THIS IS TO HELP PEOPLE WHO HAS RAN INTO PROBLEMS, (CHARITY AND HOMELESS) THIS ORGANIZATION SHOULD BE RECIEVING PROPERTY BY AUG. 15TH, AND WOULD LIKE TO HOLD OFF ON INSP. UNTIL NEW ORGANIZATION TAKES OVER. FAMILY HOUSING RESOURCES, AT THIS TIME MR EVENCHIK GAVE ME THE NAME AND NUMBER FOR CONTACT FOR FAMILY HOUSING RESOURCES, MR STEVE RUSSO, (NUMBER IN FILE) CALLED MR RUSSO AND OFFICE PERSONNEL STATED HE IS ON CONFERENCE CALL, TOOK NAME AND NUMBER FOR MR RUSSO TO RETURN CALL. PROPERTY HAS 42 UNITS, 30 ARE OCCUPIED AT THIS TIME. LEASES ON UNIT ARE 1 YEAR LEASES. ALL RESIDENTS ARE NOT AWARE OF TRANSACTION AT THIS TIME. RESIDENTS WILL NOT BE ASK TO MOVE CAN STAY IF WISHES. PROPERTY WORTH APPOX. 1.6 MILLION. |