Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FOLLOW UP CODE ENFORCE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2005 | INSP - FOLLOW UP CODE ENFORCE | Approved | AT SITE, SMOKE DETECTORS INSTALLED IN ALL ROOMS. NO PERMITS ON RECORD WITH D.S.D. FOR REQUIRED NEWLY INSTALLED FURNACE, A/C UNIT, HOT WATER HEATER. MULTIPLE VIOLATIONS IN SUB PANEL. MAIN SERVICE PANEL: DOUBLE LUGGING ON LINE SIDE AND ON LAND SIDE, TAPPING FROM METER SIDE, 2 SERVICE DISCONNECTS. BREAKER NEEDS TO FEED SUB PANEL. DOUBLE LUGGING ON LAND SIDE, NOT PROPER OVER CURRENT PROTECTION. 20 AMP RATED CONDUCTORS ON 100 AMP MAIN BREAKER. 1ST SUB PANEL: ILLEGAL FEED COMING FROM DOUBLE LUGGING ON MAIN SERVICE. 2ND SUB PANEL: ILLEGAL FEED COMING FROM DOUBLE LUGGING ON MAIN SERVICE. INPROPER OVER CURRENT PROTECTION. IMPROPER FUSING. DOUBLE LUGGING ON NEUTRAL, INCLUDING EQUIPMENT GROUNDING CONDUCTOR. |
|
| 01/05/2005 | INSP - FOLLOW UP CODE ENFORCE | Approved | AT SITE NO ONE HOME, CALLED JIAREME SERVENTTI WITH AL BROKERS. HE WILL CONTACT TENANT TO SCHEDULE RE-INSPECTION TIME WITH TENANTS. | |
| 09/22/2004 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | NOV SENT TO ALL BROKERS. | |
| 09/21/2004 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | ALL MAIL CAME BACK. WENT TO POST NOTICE ON UNIT AND TENANT INFORMED ME OF NEW OWNERS AND THEIR ADDRESS. WILL SEND NOTICE OUT TO ALL BROKERS INC. | |
| 08/16/2004 | INSP - FOLLOW UP CODE ENFORCE | Correction Required | NOV OUT. |