Permit: T04CM05627

Parcel: 14108521C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/09/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/03/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECALL AFTER FIRE PUMP WIRED
12/19/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
2. 15 KVA XFMR'S APPEAR TO BE WIRED INCORRECTLY. PROVIDE INSTRUCTIONS
12/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL ALL SUPPORT SCREWS FOR RECEPT IN INDUSTRIAL COVER
2. GROUNDING CONDUCTOR ON 30 AMP CIRCUIT NOT SIZED PROPERLY
3. SEAL OPEN KNOCK OUT
4. STRAP EMT WITHIN 3' OF PANEL
5. LOCKING DEVICE DOES NOT ALLOW PANEL COVER TO CLOSE
6. WHEN PHASE CONDUCTORS UPSIZED GROUNDING CONDUCTOR TO BE INCREASED IN SIZE
7. GROUNDING/BONDING OF XFMER'S NOT PER PLAN
8. GEC TO TERMINATE ON NEUTRAL IN XFMR
9. EMERGENCY LIGHTING NOT PER PLAN
10. HAVE 30 AMP RECEPTACLE ON 50 AMP BREAKER 120V PANELS
11. PLEASE OPEN XFMR'S FOR NEXT INSPECTION