Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/03/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECALL AFTER FIRE PUMP WIRED |
|
| 12/19/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION 2. 15 KVA XFMR'S APPEAR TO BE WIRED INCORRECTLY. PROVIDE INSTRUCTIONS |
|
| 12/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ALL SUPPORT SCREWS FOR RECEPT IN INDUSTRIAL COVER 2. GROUNDING CONDUCTOR ON 30 AMP CIRCUIT NOT SIZED PROPERLY 3. SEAL OPEN KNOCK OUT 4. STRAP EMT WITHIN 3' OF PANEL 5. LOCKING DEVICE DOES NOT ALLOW PANEL COVER TO CLOSE 6. WHEN PHASE CONDUCTORS UPSIZED GROUNDING CONDUCTOR TO BE INCREASED IN SIZE 7. GROUNDING/BONDING OF XFMER'S NOT PER PLAN 8. GEC TO TERMINATE ON NEUTRAL IN XFMR 9. EMERGENCY LIGHTING NOT PER PLAN 10. HAVE 30 AMP RECEPTACLE ON 50 AMP BREAKER 120V PANELS 11. PLEASE OPEN XFMR'S FOR NEXT INSPECTION |