Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T04CM05626
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/05/2005 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* 1) SOIL WATER TEST IS OK. 2) BLDG DRAIN IS STUBBED OUT @ TWO WAY C.O ONLY. 3) OK TO BACKFILL TRENCH. | |
07/02/2005 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) P-8 DOES NOT HAVE MINIMUM TRAP ARM DISTANCE 2) 3" HORIZONTAL WASTE HAS BACK PITCH AND IS LEVEL IN SOME AREAS. 3" REQUIRES 1/4" PER FT. 3) TWO WAY CLEANOUTS ARE REVERSED 4) DO NOT COVER |