Permit: T04CM05626


Addresses:

1840 E VALENCIA RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T04CM05626

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
07/05/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :* 1) SOIL WATER TEST IS OK. 2) BLDG DRAIN IS STUBBED OUT @ TWO WAY C.O ONLY. 3) OK TO BACKFILL TRENCH.
07/02/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) P-8 DOES NOT HAVE MINIMUM TRAP ARM DISTANCE
2) 3" HORIZONTAL WASTE HAS BACK PITCH AND IS LEVEL IN SOME AREAS. 3" REQUIRES 1/4" PER FT.
3) TWO WAY CLEANOUTS ARE REVERSED
4) DO NOT COVER