Inspection History Details
Inspection Status: Partial Approval
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2005 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) PENDING ZONING C OF O APPROVAL |
|
| 07/29/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAP OFF 2 WAY CLEANOUTS 2) HOSE BIBS MISSING VACCUM BREAKERS 3) BEDROOM AND SMOKE DETECTORS MUST BE ON ARC FAULT 4) ROOF NOT PAINTED 5) NO POWER TO SERVICE GFCI AT ROOF 6) OUTLET UNDER BREAKFAST BAR NOT ALLOWED |
|
| 07/22/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINAL GRADE NOT COMPLETE-HOUSE LOCKED 2) 2 WAY CLEANOUTS NOT CAPPED 3) SEAL KNOCKOUT AT PANEL 4) HOSE BIBS MISSING VACCUM BREAKERS 5) BEDROOMS AND SMOKIES MUST BE ON ARC FAULT 6) STOPPED INSPECTION |