Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2005 | FRAMING | Approved | IVRS - Inspection :* 1) REINSPECT DELETION OF 2 SOUTH WINDOWS ON APPROVED PLAN VERIFIED |
|
| 04/07/2005 | FRAMING | Partial Approval | IVRS - Inspection :* PARTIAL OK PENDING DELETION OF 2 SOUTH WINDOWS | |
| 04/05/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) H2.5 EVERY HOLE NAILS CEILING JOISTS SOUTH WALL 2) BLOCK MECHANICAL REFORM 3 SIDES 3) BLOCK BATH REGISTER 3 SIDES 4) FIRESTOP ALL AREAS MARKED 5) BLOCK UNDER FRONT PORCH LEDGER FASTEN 6" ON CENTER 6) STRAP AND SHIM ALL HEADERS 7) MISSING STUD REFRIG. WALL 8) DAMAGE PLATE SOUTH BATHROOM EAST WALL 9) BLOCK FRONT PORCH BELOW LEDGER FOR STUCCO MESH FASTENERS 6" 10) NOT ABLE TO LOCATE REVISION OF REMOVED WINDOWS SOUTH WALL 4 AND 5 11) TRIMMERS MISSING CLOSET DOOR SOUTHWALL 12) ANCHOR BOLTS AND NUTS MISSING THROUGHOUT MARKED |
|
| 03/30/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE SCREEN FROM DRYER VENT T-T? 2) BLOCK MECH ON 3 SIDES. 3) NO TEST ON DWV'S. 4) FIRE BLOCK DROP CEILING AREAS AND SOFFIT. 5) GROUT TUBS 6) 110 OUTLET FOR STOVE MISSING7) STRAP HEADERS AND SHIM. 8) 2 WINDOWS DELETED REVISE PLANS. 9) ELECT NOT COMPLETE. 10) STOPPED INSP. TO MANY ITEMS 11) INSP 3035, 1015 NOT APPROVED PROVIDE PROOF. 12) LATH UNDER FRONT OVERHANG NOT STAPPLED & MISSING BLOCKS |