Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM05621
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/03/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 01/31/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*I.D ALL UNITS WITH NUMBERS MEANS OF DISCONNECT ?? UNITS, ELECT. CONTRACTOR TO I.D PANEL NUMBER & CIRCUIT BRKR. NUMBER ON UNIT AS NECESSARY UNTI DATA LABELS. MARK/I.D IF PKG HEAT PUMPS HAVE AUX. HEAT STRIPS, YES OR NONE! CIRCUIT BKRS, MUST BE SIZED IN PANELS TO MATCH MIN OR MAX FUSE SIZE PROVIDE LISTING INFO FOR EXTERNAL DUCT INSULATION WRAPPING ON EAST & WEST UNITS TO ROOF. PROVIDE BRACING TO SECURE CONDENSATE BLOCKING AND CLAMPS IN POSITION. |