Permit: T04CM05616


Addresses:

7781 E RED ADOBE PS

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
02/07/2005 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
01/14/2005 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1) PVC CONDUIT TO BE BURIED PER 300.5 18"
2) WE STILL HAVE MORE THAN 360 DEGREE IN RUNS
3) VERIFY PVC GLUE IS LISTED FOR ELECTRICAL
01/10/2005 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*1) PLEASE COMPLETE 1,2,& 5 OF PREVIOUS INSPECTION
01/07/2005 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1) CORRECTLY SUPPORT RISER AND TIGHTEN SCREW FOR HUB
2) STRAP GROUNDING ELECTRODE CONDUCTOR TO WALL
3) OUTLET COVER TO BE WEATHER PROOF WEAHTER OR NOT PLUGED IN 406.8
4) GROUND RODS TO BE MINIMUM 6' APART
5) ALL PVC CONDUITS NOT ALLOWED MORE THAN 360 DEGREE IN AREA LOW VOLTAGE CONDUITS AND CABLEING TO BE INSPECTED UNDER 725.6, 800.6, 352.26 AND 300.5. EXPOSE ALL CONDUITS FOR INSPECTION