Inspection History Details
Permit: T04CM05616
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 01/14/2005 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1) PVC CONDUIT TO BE BURIED PER 300.5 18" 2) WE STILL HAVE MORE THAN 360 DEGREE IN RUNS 3) VERIFY PVC GLUE IS LISTED FOR ELECTRICAL |
|
| 01/10/2005 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :*1) PLEASE COMPLETE 1,2,& 5 OF PREVIOUS INSPECTION | |
| 01/07/2005 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1) CORRECTLY SUPPORT RISER AND TIGHTEN SCREW FOR HUB 2) STRAP GROUNDING ELECTRODE CONDUCTOR TO WALL 3) OUTLET COVER TO BE WEATHER PROOF WEAHTER OR NOT PLUGED IN 406.8 4) GROUND RODS TO BE MINIMUM 6' APART 5) ALL PVC CONDUITS NOT ALLOWED MORE THAN 360 DEGREE IN AREA LOW VOLTAGE CONDUITS AND CABLEING TO BE INSPECTED UNDER 725.6, 800.6, 352.26 AND 300.5. EXPOSE ALL CONDUITS FOR INSPECTION |