Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM05614
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/22/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PROTECT CONDUCTOR AT FITTING IN PANEL ON POLE. 2) RECEPTACLE COVER TO BE AS PER 408.6 3) NEED LABEL FOR GENERATOR AS PER PLAN AND 702.8 4) FINISH ELECTRIC IN GENERATOR ROOM. 5) FINISH OUTSIDE LIGHT AND NEED LETTER FOR APPROVAL. | |
| 03/21/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) USE APPROVED FITTING AT LB'S CHASE NIPPLES NOT APPROVED. 2) ONLY ONE CONDUCTOR PER TERMINAL LUG. 3) SEPARATE GROUDS AND NEUTRAL AT SUB PANEL. 4) BOND DISCONNECT ENCLOUSURES. 5) LABEL DISCONNECTS & PANELS. 6) CORRECTLY BOND JUNCTION BOXES NOT MOUNTING SCREWS. 7) THIGHTEN LOOSE FITTINGS. 8) A PERMANENT METAL ADDRESS LABEL IS NEEDED. 9) PLEASE PROVIDE FUSES AND REJECTION PINS. 10) USE TERMINAL CONNECTORS WITH STRANDED CONDUCTORS. 11) FINISH GROUND CONNECTIONS |