Permit: T04CM05614

Parcel: 13329001A


Addresses:

545 N CAMINO SECO


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM05614

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/23/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/22/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) PROTECT CONDUCTOR AT FITTING IN PANEL ON POLE. 2) RECEPTACLE COVER TO BE AS PER 408.6 3) NEED LABEL FOR GENERATOR AS PER PLAN AND 702.8 4) FINISH ELECTRIC IN GENERATOR ROOM. 5) FINISH OUTSIDE LIGHT AND NEED LETTER FOR APPROVAL.
03/21/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) USE APPROVED FITTING AT LB'S CHASE NIPPLES NOT APPROVED. 2) ONLY ONE CONDUCTOR PER TERMINAL LUG. 3) SEPARATE GROUDS AND NEUTRAL AT SUB PANEL. 4) BOND DISCONNECT ENCLOUSURES. 5) LABEL DISCONNECTS & PANELS. 6) CORRECTLY BOND JUNCTION BOXES NOT MOUNTING SCREWS. 7) THIGHTEN LOOSE FITTINGS. 8) A PERMANENT METAL ADDRESS LABEL IS NEEDED. 9) PLEASE PROVIDE FUSES AND REJECTION PINS. 10) USE TERMINAL CONNECTORS WITH STRANDED CONDUCTORS. 11) FINISH GROUND CONNECTIONS