Permit: T04CM05611

Parcel: 140324000

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T04CM05611

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/19/2005 BUILDING - FINAL Approved IVRS - Inspection :*
1) REINSPECT
07/14/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAXIMUM ALLOWED A/C FUSE 40 AMP-50 AMP INSTALLED
2) SEAL HOLES IN GARAGE CEILING
3) NO A/C REGISTERS OR FANS
4) KITCHEN ISLAND GFCI CANNOT BE UNDER OVERHANG OF 6" OR MORE
5) BARE WIRES ENTRY
6) LABEL SMOKE DETECTOR CIRCUIT IN PANEL
7) BEDROOM SMOKE DETECTORS MUST BE ON ARC FAULT CIRCUIT
8) STOPPED INSPECTION-TO MANY ITEMS