Permit: T04CM05596

Parcel: 11303033A

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
07/05/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
1) FREEZE BOARDS PER DETAILS AZ SECTION 1
06/30/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSED ROWS AT NORTH END
2) NEED STUD CLIPS, HEADER STRAPS AND TOP PLATED STRAPPED OR OSB'D
3) H2.5 LEDGERS WHERE A-35 TABS ARE NOT FOLDED
06/09/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BRACED WALL PANELS NOT PER PLAN
2) NAILING SET TO DEEP OR STICKING UP
3) FILL ALL HOLES H2.5'S-A-35'S
4) INSTALL BOLTS EACH END BRACED WALL PANELS
5) INSTALL BOLTS WITHIN 12" EACH END BOTTOM PLATES
6) PORCH NOT FRAMED PER PLAN
7) STOPPED INSPECTION