Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/12/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ROOF DRAIN, OVERFLOW REQUIRED ROOF DRAIN, PUT ON COVERS 2) LABEL NOT H20 BONDED SYSTEM IN SERVICE PANEL 3) NEED HOUSE ADDRESS 4) NEED PIPE DOPE AT REAR GAS COCK 5) ROOF DRAINAGE EROSION S/E SIDE 6) LOOSE RECEPTACLES IN GARAGE 7) GAS COCK LAUNDRY-PIPE DOPE 8) LOOSE OUTLETS IN STUDY 9) DBL LAV. REQUIRES DBL OUTLET 10) GFCI PROTECTION FOR JACUZZI 11) COVER PLATE FOR MICRO BOX |