Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM05570
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/09/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE FRESH AIR INTAKES ON 3 PACKAGE UNITS. 2. BLOCK & CLAMP CONDENSATE DRAINS & EXTEND OVER TO ROOF DRAINS. 3. USE A PROPER FITTING AT TRANSITION TO PVC. 4. PAINT PVC & BLOCK EVERY 4'. 5. MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. 6. PERMANENTLY I.D UNITS & DISCONNECTS. 7. PROVIDE PLUG IN CLEANOUT. |
|
| 01/08/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTRACTOR PLEASE CALL ME I NEED PLANS, ACCESS TO ROOF, ETC. |
|
| 12/29/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO CONTRACTOR ON SITE |
|
| 08/25/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO OCCUPY ROOM 201 |