Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM05570
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PLANS STILL DO NOT HAVE WILDAN STAMP OK ELECTRICAL ITEMS |
|
| 01/08/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE HAVE SOMEONE ON SITE TO ACCESS EQUIPMENT AND PLANS. |
|
| 12/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BACK FED BREAKER TO USE MANUFACTURERS HOLDOWN 2) PVC CONDUIT TO BE AS PER 300.5 3) FUSES NOT PER PLANS 4) TAPS NOT PER PLANS, PLEASE VERIFY TRP ? 240.21 5) PLANS DO NOT HAVE CITY STAMP-3RD INSPECTION 6) TIGHTEN LOOSE FITTINGS AND STRAPS-USE APPROVED STRAPING METHODS 7) PLEASE RELEASE REFEE BEFORE NEXT INSPECTION |
|
| 05/03/2006 | ELECTRIC - FINAL | Partial Approval | 1. ONLY ONE CONDUCTOR PER LUG. 2. LABEL DISCONNECTS. 3. NEED CITY STAMPED REVISED ELECTRICAL PLANS ON SITE. OK ROOF |
|
| 05/01/2006 | ELECTRIC - FINAL | Cancelled | IVRS - AP canceled | |
| 04/28/2006 | ELECTRIC - FINAL | Denied | PLEASE SET UP MEETING WITH ELECTRICAL CONTRACTOR TO REVIEW FINAL AND OPEN EQUIPMENT. | |
| 04/26/2006 | ELECTRIC - FINAL | Cancelled | IVRS - AP canceled | |
| 01/06/2006 | ELECTRIC - FINAL | Partial Approval | ||
| 08/29/2005 | ELECTRIC - FINAL | Partial Approval | 1) OK FOR C OF O | |
| 08/25/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING. 314.20-METAL NOT APPROVED (LIGHT BOXES) |