Permit: T04CM05570

Parcel: 12708203A


Addresses:

5335 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM05570

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PLANS STILL DO NOT HAVE WILDAN STAMP

OK ELECTRICAL ITEMS
01/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLEASE HAVE SOMEONE ON SITE TO ACCESS EQUIPMENT AND PLANS.
12/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BACK FED BREAKER TO USE MANUFACTURERS HOLDOWN
2) PVC CONDUIT TO BE AS PER 300.5
3) FUSES NOT PER PLANS
4) TAPS NOT PER PLANS, PLEASE VERIFY TRP ? 240.21
5) PLANS DO NOT HAVE CITY STAMP-3RD INSPECTION
6) TIGHTEN LOOSE FITTINGS AND STRAPS-USE APPROVED STRAPING METHODS
7) PLEASE RELEASE REFEE BEFORE NEXT INSPECTION
05/03/2006 ELECTRIC - FINAL Partial Approval 1. ONLY ONE CONDUCTOR PER LUG.
2. LABEL DISCONNECTS.
3. NEED CITY STAMPED REVISED ELECTRICAL PLANS ON SITE.
OK ROOF
05/01/2006 ELECTRIC - FINAL Cancelled IVRS - AP canceled
04/28/2006 ELECTRIC - FINAL Denied PLEASE SET UP MEETING WITH ELECTRICAL CONTRACTOR TO REVIEW FINAL AND OPEN EQUIPMENT.
04/26/2006 ELECTRIC - FINAL Cancelled IVRS - AP canceled
01/06/2006 ELECTRIC - FINAL Partial Approval
08/29/2005 ELECTRIC - FINAL Partial Approval 1) OK FOR C OF O
08/25/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING. 314.20-METAL NOT APPROVED (LIGHT BOXES)