Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2005 |
MECHANICAL - FINAL |
|
Approved |
OK FOR FINAL C OF O |
| 03/10/2005 |
MECHANICAL - FINAL |
|
Approved |
PERMANENTLY IDENTIFY ALL EQUIPMENT W/SUITE #. NO INK. 60 AMP FUSES TOO BIG FOR RHEEM UNIT. VENT ON CONDENSATE TRAP MUST BE DOWNSTREAM OF THE TRAP. CHECKED DUCT SMOKE DETECTORS. SECURE WATER HEATER VENT IN ATTIC. |