Permit: T04CM05544

Parcel: 13414011A


Addresses:

401 S PRUDENCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
05/16/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :* #1 FROM INSPECTION 5-11-05 DONE. #2 NEW BOXES BY ELECTRICAL CONTRACTOR SUPPORTED. OLD WORK TO REMAIN AS IS.
05/11/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* 1) VDV CABLEING TO BE AS PER 725.2,725.6 800.2 & 800.6 2) BOXES NEED SUPPORT WIRES 3) FILL UNUSED OPENINGS. OK TO TILE EXCEPT AREAS FOR ELECTRICAL ACCESS.