Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/04/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* OK FINAL |
| 01/28/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) WHERE IS STAMPED REVISED PLAN? |
| 01/27/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) MULTIWIRE BRANCH CIRCUITS SUPPLYED TO SAME YOKE TO DISCONNECT UNGROUNDED CONDUCTORS SIMULTANEOUSLY 210.7 (C) 2) PLEASE HAVE REVISED FIXTURE SCHEDULD STAMPED AND APPROVED. |