Permit: T04CM05518

Parcel: 116031940


Addresses:

2110 W BRICHTA DR


Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Permit Number - T04CM05518

Inspection Description - PLUMBING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
08/18/2006 PLUMBING - PROGRESS Approved IVRS - Inspection :*
01/04/2006 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*CORRECTION MADE OK
OK TO COVER UNDER GROUND
I NEED TO SEE VENT CONTINUATION FOR G.T AND FLOOR DRAIN
01/03/2006 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection :*VENT FITTING TO OPEN IN THE DIRECTION OF FLOW.
I CALLED DOC AND LEFT A MESSAGE ON HIS VOICE MAIL
12/28/2005 PLUMBING - PROGRESS Partial Approval IVRS - Inspection :*GREASE TRAP REQUIRES PROPER VENTING DOWNSTREAM. SAME WITH P-1
TRAPS ARE TO BE VENTED DOWNSTREAM IN AN APPROVED MANNER.
G.T ( VENT THE GT)
NOT THE HORIZONTAL DRAIN
ADD CLEAN OUT AT 4" CHANGE OF DIRECTION
PROVIDE FLOW TEST