Permit: T04CM05494

Parcel: 140377380


Addresses:

6937 S WINGBOW DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/14/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/08/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/02/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/01/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ISLAND GFCI
2) BARE WIRES IN ISLAND
3) NO POWER ONE GFCI CIRCUIT
4) SECURE A/C WHIP WITHIN 12" OF DISCONNECT
5) LABEL ARC FAULT CIRCUITS
6) 1/2 BATH REQUIRES GFCI OUTLET
7) BATHROOM GFCI'S HOT WHEN TRIPPED
8) NEED SPECIAL INSPECTION REPORT