Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/25/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MINIMUM TREAD DEPTH FOR WINDERS IS 6" (IRC 311.5.3.2) 2) OVER KINKED FLEX DUCT IN LIVING ROOM |
|
| 05/16/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) TRUSS H2.5 CLIP NOT NAILED 2) LVL NOT NAILED PER PLAN 3) HIGH/LOW COMBUSTION AIR CANNOT BE CONNECTED-BLOCK 4) RED HEAD ANCHOR BOLTS LOOSE 5) P-2 GARAGE SHEAR MISSING ANCHOR BOLTS PER 5-1 NOTE C 6) 10/SD4 NOT COMPLIED WITH AT KITCHEN PANTRY 7) HOUSE NOT COMPLETE ENOUGH TO INSPECT. SUPERINTENDENT TO INSURE HOUSE IS PER PLAN AND CODE PRIOR TO CALLING FOR INSPECTION 8) PROVIDE A PLAN WITH ALL PAGES IN ORDER |