Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/19/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - FINISH WC INSTALLATION - ROTATE IRR RP TO PROVIDE ACCESS TO REPAIR RELIEF ASSEMBLY - PROVIDE CERT - T&P TO TERMINATE 6"-24" ABV GRADE. |
|
| 09/18/2006 | PLUMBING - FINAL | Denied | - A PVB IS THE CORRECT DEVICE FOR BACKFLOW PREVENTION AT IRRIGATION SUPPLY. - ASSEMBLY SHALL BE CERTIFIED AFTER INSTALLATION - COMPLETE INSTALLATION OF HB VAC BREAKER - CLEANOUT PLUGS SHALL BE MADE WATER AND GAS TIGHT - PROTECT VENT PENETRATIONS W/LATEX PAINT - SEAL WALL PENETRATIONS OPEN FRONT TOILET SEAT. |