Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM05458
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/23/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/22/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO COMMENTS ON PAPERWORK |
|
02/22/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FOR C OF O . PROVIDE ACCEPTANCE LETTER FROM ARCH. REGARDING ELEC. CHANGES ON PANEL. OTHERWISE THIS IS OK TO FINAL | |
02/17/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLANS CALL FOR 3 ( PHASE) 42 CIR. PANEL "A-1" NOT SINGLE PHASE 24 ??PANEL. 2) CORRECT PANEL SCHEDULE. 3) REVISE PLANS & SUBMIT FOR PLAN REVIEW ( THE WASY THIS IS WIRED WILL CHANGE THE LOAD CALCULATIONS) PLEASE HAVE CITY APPROVED REVISED DRAWINGS ON SITE AT NEXT ELEC. FINAL INSP. |