Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/22/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO COMMENTS ON PAPERWORK |
|
| 02/22/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FOR C OF O . PROVIDE ACCEPTANCE LETTER FROM ARCH. REGARDING ELEC. CHANGES ON PANEL. OTHERWISE THIS IS OK TO FINAL | |
| 02/17/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLANS CALL FOR 3 ( PHASE) 42 CIR. PANEL "A-1" NOT SINGLE PHASE 24 ??PANEL. 2) CORRECT PANEL SCHEDULE. 3) REVISE PLANS & SUBMIT FOR PLAN REVIEW ( THE WASY THIS IS WIRED WILL CHANGE THE LOAD CALCULATIONS) PLEASE HAVE CITY APPROVED REVISED DRAWINGS ON SITE AT NEXT ELEC. FINAL INSP. |