Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/28/2005 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* REMOVE FLEX DUCT FROM DRYER VENT. REMOVE SCREWS FROM DRYER VENT, USE POP RIVETS IF NECESSARY TERMINATE DRYER VENT INTO A T-TOP. WILL CHECK WATER HEATER VENT & FRYER CORRECTIONS ON ABOVE CEILING. OK FOR SHEET ROCK. EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE. PROVIDE AN APPROVED CAP ON WATER HEATER VENT. HORIZONTAL SECTION OF AFTER HEATER VENT NOT TO EXCEED 75% OF TOTAL HEIGHT. PROVIDE REVISION FROM ENGINEER IF DELETING COMBUSTION AIR VENTS. |