Permit: T04CM05427

Parcel: 126110150


Addresses:

4327 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/28/2005 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :* REMOVE FLEX DUCT FROM DRYER VENT. REMOVE SCREWS FROM DRYER VENT, USE POP RIVETS IF NECESSARY TERMINATE DRYER VENT INTO A T-TOP. WILL CHECK WATER HEATER VENT & FRYER CORRECTIONS ON ABOVE CEILING. OK FOR SHEET ROCK. EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE. PROVIDE AN APPROVED CAP ON WATER HEATER VENT. HORIZONTAL SECTION OF AFTER HEATER VENT NOT TO EXCEED 75% OF TOTAL HEIGHT. PROVIDE REVISION FROM ENGINEER IF DELETING COMBUSTION AIR VENTS.