Permit: T04CM05427

Parcel: 126110150


Addresses:

4327 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/14/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK FINAL
02/09/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*1) M/C CABLE TO EXHAUST FAN TO TERMINATE INTO A FITTING 2) SUPPORT UP ALL VDV CABLES 325.6 & 800.6 3) TWIN BREAKERS BROKEN OUT BOSS? STAB POSSING POTENTIAL ARC HAZARD. PLEASE INSTALL BREAKER TO PREVENT. 4) USE AN APPROVED EXTENDER RUG AT COMBUSTABLE 5) CHAIRS AND RECEPTACLES ARE EXISTING