Permit: T04CM05424

Parcel: 116270060


Addresses:

3003 W BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/30/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
NEED TO SEAL RACEWAY AT ROOF FOR ALARM GROUND AND ARRANGE GROUND TO PROTECT IT.
11/20/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. NEED EMERGENCY LIGHTING FIXTURES.
2. GFI PROTECT FOUNTAIN.
3. PROVIDE INSPECTION FOR POOL BONDING/WIRING.
4. PROVIDE ALARM PANEL EARTH GROUND (ADT - SEE INTRUCTIONS ON PANEL).
11/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
PARTIAL INSPECTION ONLY FOR INTERIOR OF MAIN BUILDING AND ROOFTOP.

1. BATH LIGHT FIXTURES NOT FLUSH/TILE HINDERS
NEC 110.3, 12
2. INSTALL W.P COVER ON EXTERIOR GFI - NEC 406.8
3. PANEL DIRECTORY'S NOT COMPLETE OR CORRECT -
NEC 408.4
4. PROVIDE GFI PROTECTION FOR KITCHEN RECEPTACLES - NEC 210.8 (B)
5. IDENTIFY SERVICE DISCONNECTS THEY ARE NOT "MAIN" DISCONNECTS - NEC 230.70 (C)
6. EMERGENCY/EXIT LIGHTING NOT WORKING AND MAKE SURE THEY COMPLY WITH NEC 700.12
7. DISPOSAL RECEPTACLE NOT COMPLETE AND WHERE IS DISHWASHER CKT?
8. CKT TO ANSUL SYSTEM NOT PROPERLY WIRED/STRAPPED

PARTIAL INSPECTION ONLY: NEED TO CALL IN POOL INSPECTION. I WILL INSPECT POOL/RAMADE SITE
ELECTRICAL NEXT INSPECTION.