Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* NEED TO SEAL RACEWAY AT ROOF FOR ALARM GROUND AND ARRANGE GROUND TO PROTECT IT. |
|
| 11/20/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED EMERGENCY LIGHTING FIXTURES. 2. GFI PROTECT FOUNTAIN. 3. PROVIDE INSPECTION FOR POOL BONDING/WIRING. 4. PROVIDE ALARM PANEL EARTH GROUND (ADT - SEE INTRUCTIONS ON PANEL). |
|
| 11/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PARTIAL INSPECTION ONLY FOR INTERIOR OF MAIN BUILDING AND ROOFTOP. 1. BATH LIGHT FIXTURES NOT FLUSH/TILE HINDERS NEC 110.3, 12 2. INSTALL W.P COVER ON EXTERIOR GFI - NEC 406.8 3. PANEL DIRECTORY'S NOT COMPLETE OR CORRECT - NEC 408.4 4. PROVIDE GFI PROTECTION FOR KITCHEN RECEPTACLES - NEC 210.8 (B) 5. IDENTIFY SERVICE DISCONNECTS THEY ARE NOT "MAIN" DISCONNECTS - NEC 230.70 (C) 6. EMERGENCY/EXIT LIGHTING NOT WORKING AND MAKE SURE THEY COMPLY WITH NEC 700.12 7. DISPOSAL RECEPTACLE NOT COMPLETE AND WHERE IS DISHWASHER CKT? 8. CKT TO ANSUL SYSTEM NOT PROPERLY WIRED/STRAPPED PARTIAL INSPECTION ONLY: NEED TO CALL IN POOL INSPECTION. I WILL INSPECT POOL/RAMADE SITE ELECTRICAL NEXT INSPECTION. |