Permit: T04CM05423

Parcel: 140295310

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/29/2005 FRAMING Approved IVRS - Inspection :*
03/24/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL ALL LATH PENETRATIONS
2) 10/SD4 NOT PER PLAN
3) WATER LINES MUST BE 12" FROM CAN LIGHTS
4) 1" CLEARANCE FROM COMBUSTIBLES AT B-VENT
5) LOOSE ANCHOR BOLTS THROUGHOUT
6) NO TEST ON DWV'S
7) STOPPED INSPECTION