Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM05423
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/29/2005 | FRAMING | Approved | IVRS - Inspection :* | |
03/24/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL ALL LATH PENETRATIONS 2) 10/SD4 NOT PER PLAN 3) WATER LINES MUST BE 12" FROM CAN LIGHTS 4) 1" CLEARANCE FROM COMBUSTIBLES AT B-VENT 5) LOOSE ANCHOR BOLTS THROUGHOUT 6) NO TEST ON DWV'S 7) STOPPED INSPECTION |