Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :*OK FOR CEILING TILES 2ND LAYER FIRE WRAP OK |
|
| 12/07/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | CHECKED 1ST LAYER FIRE WRAP O.K. TO PROCEED W/2ND LAYER | |
| 12/05/2005 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999*CANNOT CHECK OVERLAP ONJOINTS & SEAMS WITH FOIL TAPE ON EVERYTHING. INSTALLER DIDN'T FOLLOW INSTALL INSTRUCTIONS FOR BANDING 1ST LAYER OF INSULATION. PROVIDE ACCESS UP INTO ATTIC. |
|
| 12/01/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CHECKED WELDS ON GREASE DUCT OK FOR FIRE WRAP |