Permit: T04CM05420

Parcel: 127023460


Addresses:

755 N MAGNOLIA AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
11/03/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*GAS PRESSURE TEST IS OK
DWV WATER TEST TO TOP OF VTR IS OK
OVERHEAD WATER DISTRIBUTION IS OK
11/01/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/26/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/25/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*SHALL PROVIDE A VENT FOR THE INTERCEPTOR.
SHALL PROVIDE A WATER TEST ON DWV SYSTEM ALL THE WAY TO THE TOP OF VENT THRU ROOF
SHALL PROVIDE A DUTCHMAN AND USE REQUIRED PACKING IRONS FOR CLOSET RINGS.
SHALL PROVIDE DIRECTIONAL FITTINGS FOR C.O WITH EXTENTIONS
10/18/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*