Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/21/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS #6 & 7 OF 6/9/06 AND 4, 6 & 8 OF 2/1/06 1. NEED TO CHECK ABOVE WALK-IN BOX |
|
| 06/09/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GROUND TO BE GREEN ENTIRE LENGTH. NEUTRAL NOT TO BE UNGROUNDED COLORS MARKED WHITE. 2. PLASTIC BUSHINGS FOR CONDUCTOR #'S & LARGER. 3. IDENTIFY UNGROUNDED CONDUCTORS PER 210.5(C) AMENDMENTS. 4. RECEPTACLE COVER UNDER DISHWASHER/SINK TO BE BUBBLE COVER. 5. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS. 314.20 6. WHERE IS CIRCUIT & LOADS FOR MOTOR TO ROLL DOOR. 7. MAINTAIN WORKING CLEARANCE AT A/C DISCONNECTS. 8. PREVENT DIE ELECTRIC CONTACT. 9. TIGHTEN LOOSE FITTINGS. 10. BOND ENCLOSURE. 11. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO. 406.8 12. FINISH PREVIOUS ITEMS. |
|
| 01/03/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*PROVIDE LETTER ON TORQINE OF BUST CONNECTIONS AND TERMINATIONS @ LUGS & CONDUCTORS |