Permit: T04CM05414

Parcel: 140376240


Addresses:

6959 S GOSHAWK DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/31/2005 FRAMING Approved IVRS - Inspection :*
05/27/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GARAGE P-2 SHEAR WALL MISSING ANCHOR BOLTS AT 16" ON CENTER UNDER STAIRS
2) INTERIOR BEARING WALL REQUIRES 2 ANCHOR BOLTS
3) SEWER DRAIN REQUIRES 1/4" PER FT. PITCH
05/24/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOLDOWNS MISSING
2) NAIL PROTECT ROMEX AT KITCHEN
3) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR
4) NO ELECTRICAL IN ATTIC
5) KITCHEN ROMEX MUST BE STAPLED WITHIN 8" FROM BOX
05/23/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NOT COMPLETE
05/18/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) LVL MUST BE CONTINOUS LVL NOT ADDED O.S.B., PROVIDE ENGINEERS APPROVED REPAIR OR REPLACE O.S.B.
2) LVL NOT NAILED PER PLAN
3) SHEAR BLOCKING PANELS NOT NAILED PER 6/SD2
4) HOLDOWNS NOT IN
5) P-2 SHEARWALL ANCHOR BOLTS NOT IN PER NOTE C S-1
6) INTERIOR BEARING WALL MISSING ANCHOR BOLTS
7) TRUSS F4 NOT BEARING ON WALL
8) TRUSS F3 NOT BEARING
9) SEWER DRAIN REQUIRES 1/4" PER FT FALL
10) SEAL FLOOR PENETRATIONS
11) BEARING WALL SILL PLATES REQUIRE 2 ANCHOR BOLTS ON SILL PLATES
12) STUDS MUST BEAR ON SILL PLATES
13) HAND RAIL BLOCKS TO LOW
14) P-1 SHEARWALL MISSING
15) 2ND FLOOR SILL PLATES NOT NAILED PER PLAN
16) STOPPED INSPECTION
05/17/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER JAMES