Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/27/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GARAGE P-2 SHEAR WALL MISSING ANCHOR BOLTS AT 16" ON CENTER UNDER STAIRS 2) INTERIOR BEARING WALL REQUIRES 2 ANCHOR BOLTS 3) SEWER DRAIN REQUIRES 1/4" PER FT. PITCH |
|
| 05/24/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HOLDOWNS MISSING 2) NAIL PROTECT ROMEX AT KITCHEN 3) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR 4) NO ELECTRICAL IN ATTIC 5) KITCHEN ROMEX MUST BE STAPLED WITHIN 8" FROM BOX |
|
| 05/23/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NOT COMPLETE |
|
| 05/18/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) LVL MUST BE CONTINOUS LVL NOT ADDED O.S.B., PROVIDE ENGINEERS APPROVED REPAIR OR REPLACE O.S.B. 2) LVL NOT NAILED PER PLAN 3) SHEAR BLOCKING PANELS NOT NAILED PER 6/SD2 4) HOLDOWNS NOT IN 5) P-2 SHEARWALL ANCHOR BOLTS NOT IN PER NOTE C S-1 6) INTERIOR BEARING WALL MISSING ANCHOR BOLTS 7) TRUSS F4 NOT BEARING ON WALL 8) TRUSS F3 NOT BEARING 9) SEWER DRAIN REQUIRES 1/4" PER FT FALL 10) SEAL FLOOR PENETRATIONS 11) BEARING WALL SILL PLATES REQUIRE 2 ANCHOR BOLTS ON SILL PLATES 12) STUDS MUST BEAR ON SILL PLATES 13) HAND RAIL BLOCKS TO LOW 14) P-1 SHEARWALL MISSING 15) 2ND FLOOR SILL PLATES NOT NAILED PER PLAN 16) STOPPED INSPECTION |
|
| 05/17/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER JAMES |