Permit: T04CM05413

Parcel: 140376160


Addresses:

6913 S GOSHAWK DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/01/2005 FRAMING Approved IVRS - Inspection :*
05/31/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) U24 HANGER MISSING NAILS
2) P-3 SHEAR REQUIRES A.B.'S AT 16" ON CENTER
3) NAIL PROTECT WIRES AND PLUMBING WITHIN 1 1/4" OF STUD SURFACE
4) SEWER VENT CANNOT BE WITHIN 10 FT OF INTAKE AIR
5) SHIM HEADERS
6) STACK OUT OF WALL CAVITY AT PANTRY
7) FILL 2ND FLOOR DWV
05/25/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
05/10/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NO PRIOR INSEPCTION REPORT ON SITE
2) MANY ANCOR BOLTS MISSING THRU-OUT
3) LVL BEAM NOT NAILED PER PLAN
4) LVL HAS INCORRECT HANGERS
5) P-3 SHEAR WALL NOT NAILED PER PLAN NAILS DRIVEN TO DEEP
6) PROVIDE 12 EACH A35 AT P3 SHEAR PER PLAN
7) ANCHOR BOLTS LOOSE
8) STOPPED INSPECTION-TO MANY ITEMS
9) SUPERINTENDENT TO INSURE HOUSE IS COMPLETE PRIOR TO NEXT INSPECTION. NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE
05/09/2005 FRAMING Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
1) NO PLANS OR PERMIT ON SITE
05/06/2005 FRAMING Cancelled IVRS - RI canceled