Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM05404
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/04/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/03/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SMOKE DETECTORS ARE NOT ALLOWED TO BE MOUNTED CLOSER THAN THREE ( 3') FEET TO ANY AIR REGISTER. THIS IS TO PREVENT THE SUPPLY AIR FROM BLOWING ANY SMOKE CLEAR OF THE DETECTOR. 2) THE SMOKE DETECTOR MUST NOT BE CLOSER THAN SIX ( 6) INCHES TO THE WALL AND NOT FARTHER THAN 12" . THIS IS SAME IF MOUNTED ON WALL OR CEILING. PLEASE CORRECT & RECALL INSPECTION. THANKS. PS. ALL OUTLETS IN BEDROOMS MUST BE ON ARC FAULT PROTECTED CIRCUITS. MAC 909- 5147 |
|
01/26/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The smoke detectors have not been installed per code.| 165* SMOKE DETECTORS MUST BE INSTALLED IN BEDROOMS THEY MUST BE INTER CONNECTED TO ALARM SIMULTANEOULSLY, AND THEY MUST BE BOTH ELECTRICAL AND BATTERY POWERED. THANKS CORRECT & RECALL |