Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 04/25/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 4 AND 5 OF 4/19/05 NOT COMPLIED WITH |
|
| 04/19/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RED HEAD ANCHOR BOLTS LOOSE 2) BEARING STUDS NOTCHED MORE THAN 25 PERCENT-REPLACE. ALSO AT SHEARWALLS 3) HEADERS MUST BEAR ON TRIMMERS 4) NO DWV WATER TEST 5) FIRE BLOCK RANGE DUCT 6) SECURE DEAD WOOD OVER BATH AND CLOSETS 7) SHEAR BLOCKING PANELS NOT NAILED PER 14/DT1 |