Permit: T04CM05398

Parcel: 140382660


Addresses:

5919 E CHAUCERS DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/26/2005 FRAMING Approved IVRS - Inspection :*
04/25/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) ITEMS 1, 2, 5, 7 AND 8 FROM 4/19/05 NOT COMPLIED WITH
2) STOPPED INSPECTION, TOO MANY ITEMS
3) NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE
04/19/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACE
2) SHEARWALL AND BEARING WALL STUDS NOTCHED GREATER THAN 25 PERCENT-REPLACE THEM
3) HEADERS MUST BEAR ON TRIMMERS
4) PEX NOT ALLOWED WITHIN 12" OF CAN LIGHTS
5) NO DWV WATER TEST
6) NO POTABLE WATER TEST
7) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE
8) RED HEAD ANCHOR BOLTS LOOSE
9) STOPPED INSPECTION TO MANY ITEMS