Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 04/25/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) ITEMS 1, 2, 5, 7 AND 8 FROM 4/19/05 NOT COMPLIED WITH 2) STOPPED INSPECTION, TOO MANY ITEMS 3) NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE |
|
| 04/19/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACE 2) SHEARWALL AND BEARING WALL STUDS NOTCHED GREATER THAN 25 PERCENT-REPLACE THEM 3) HEADERS MUST BEAR ON TRIMMERS 4) PEX NOT ALLOWED WITHIN 12" OF CAN LIGHTS 5) NO DWV WATER TEST 6) NO POTABLE WATER TEST 7) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 8) RED HEAD ANCHOR BOLTS LOOSE 9) STOPPED INSPECTION TO MANY ITEMS |