Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM05381
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
09/18/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NOTE: AREA OCCUPIED WITHOUT FINAL APPROVAL 1) THIS IS A 265V UNIT, BOND BOSHING NEEDED FOR CONCENTRICS ABOVE 250V 250.92 2) CIELING CANS COUNTERED WITHOUT FOLLOWUP INSPECTION 3) SHEET METAL SCREW NOT ALLOWED FOR GROUNDING |
|
08/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection 1) NO WORK PROGRESS 2) A REFEE HAS BEEN ACCESSED PER ADMIN CODES |
|
08/09/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN LOOSE SEAL TITE FITTINGS 2) PROPERLY IDENTIFY CONDUCTORS AND DISCONNECT FOR A/C 3) USE CORRECT SIZED CONDUCTORS FOR AMPACITY 4) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS 5) WHERE ARE REVISED LIGHTING PLANS AS PER LAST INSPECTION 6) NOTE: AREA OCCUPIED WITHOUT FINAL APPROVAL |
|
06/27/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ROOM # 105 OK TEMP C OF O | |
06/15/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SWITCHES TO BE GROUNDED. 2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 METAL NOT APPROVED. 3) BATH CANNOT AS PER PLANS-BULB. 4) BATH FIXTURE HAS BROKEN LAMB HOLDER. |