Permit: T04CM05381

Parcel: 11011176E


Addresses:

2500 N ROSEMONT BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM05381

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/22/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
09/18/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NOTE: AREA OCCUPIED WITHOUT FINAL APPROVAL
1) THIS IS A 265V UNIT, BOND BOSHING NEEDED FOR CONCENTRICS ABOVE 250V 250.92
2) CIELING CANS COUNTERED WITHOUT FOLLOWUP INSPECTION
3) SHEET METAL SCREW NOT ALLOWED FOR GROUNDING
08/12/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) NO WORK PROGRESS
2) A REFEE HAS BEEN ACCESSED PER ADMIN CODES
08/09/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN LOOSE SEAL TITE FITTINGS
2) PROPERLY IDENTIFY CONDUCTORS AND DISCONNECT FOR A/C
3) USE CORRECT SIZED CONDUCTORS FOR AMPACITY
4) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS
5) WHERE ARE REVISED LIGHTING PLANS AS PER LAST INSPECTION
6) NOTE: AREA OCCUPIED WITHOUT FINAL APPROVAL
06/27/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* OK ROOM # 105 OK TEMP C OF O
06/15/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) SWITCHES TO BE GROUNDED. 2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 METAL NOT APPROVED. 3) BATH CANNOT AS PER PLANS-BULB. 4) BATH FIXTURE HAS BROKEN LAMB HOLDER.