Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 04/20/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) BREAK THRU OPENINGS TO EXISTING HOUSE NOT MADE 2) SHOWER REQUIRES TEMP/PRESSURE ANTI-SCALD VALVE PRIOR TO FINAL |
|
| 04/18/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) OPENINGS PENDING |
|
| 04/08/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 4 EACH HP5A HOLDOWNS REQUIRED 2) RAFTERS REQUIRE H2.5 CLIPS TO TOP AND BOTTOM PLATE OR SOLID SHEATHING 4) WINDOW AND DOOR OPENING REQUIRE DBL 2 X 6 HEADERS BEARING ON TRIMMER STUDS SEE DETAIL 4/2 5) STUDS REQUIRED AT 16" ON CENTER BEARING WALL 6) WIRES CANNOT BE SPLICED IN WALL MUST SPLICE IN EXPOSED ELECTRIC BOX 7) BUSHINGS REQUIRED IN ELECTRIC BOX KNOCK OUTS 8) NAIL PROTECT ALL WIRES AND PLUMBING WITHIN 1 1/4" OF WALL SURFACE 9) EXPOSE ROUGH PLUMBING LINES 10) CONNECT ALL GROUND WIRES IN ELECTRIC BOXES AND SECURE WITH A MECHANICAL FASTENER 11) BEDROOMS REQUIRE HARD WIRED SMOKE DETECTORS |
|
| 03/28/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE BEARING WALL STUDS AT 16" ON CENTER AS PER PLAN |