Permit: T04CM05378

Parcel: 130170090


Addresses:

4126 E 27TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/09/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/07/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND METAL BOXES AND PROTECT WHERE NEEDED
2) SECURE WIRE WITHIN IN 12" OF BOXES
3) STRIP WIRES AT BOXES
4) SEPERATE DBL TAPED BREAKER
5) LOCK OFF PANEL
6) NEED GFI TEMP POWER OUTLET