Inspection Status: Approved
Inspection History: MECHANICAL - HOOD SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 05/24/2005 |
MECHANICAL - HOOD SYSTEMS |
|
Approved |
|
| 03/31/2005 |
MECHANICAL - HOOD SYSTEMS |
|
Partial Approval |
IVRS - Inspection :* PIZZA OVEN EXH DUCT. OK TO COVER |
| 03/28/2005 |
MECHANICAL - HOOD SYSTEMS |
|
Partial Approval |
IVRS - Inspection :* 1) SINGLE WALL VENT, PIZZA OVERN?? INTO VERTICLE OFFSET, OK TO FINISH WRAP. 2) OK TO COMPLETE WRAP, TOP OF HOOD, OFFSET OVER INTO VERTICLE DUCT IN CHASE |
| 03/17/2005 |
MECHANICAL - HOOD SYSTEMS |
|
Partial Approval |
IVRS - Inspection :* |
| 03/16/2005 |
MECHANICAL - HOOD SYSTEMS |
|
Partial Approval |
IVRS - Inspection :* INSPECTED PIZZA OVEN DUCT. OK TO FIRE WRAP |
| 03/02/2005 |
MECHANICAL - HOOD SYSTEMS |
|
Partial Approval |
IVRS - Inspection :* WHERE IS STRUCT. SUPPORT ON CENTER SECTION? WRAPPED SECTION OK |
| 02/28/2005 |
MECHANICAL - HOOD SYSTEMS |
|
Partial Approval |
IVRS - Inspection :* 16 GA TYPE I EXH. DUCT, OK TO APPLY FIRE WRAP |
| 02/24/2005 |
MECHANICAL - HOOD SYSTEMS |
|
Not ready for Inspection |
IVRS - Inspection :* 1) COORDINATE SO EXHAUST DUCT, HANGERS CALL ALL BE CHECKED WHEN COMMENCING. 2) SUSPENDED ROUGH DUCT-AIR HANDLERS, ETC, ONLY |