Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04CM05371
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS MADE OK. 2) PLUMBING FINAL OK. 3) OK FOR C OF O PENDING ANY OTHER INSPECTION. | |
06/16/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* DIRECTLY TRAPPED MEANS AT THE FIXTURE/APPLIANCE TRAP TO BE INSTALLED PER DIAGRAM. | |
06/15/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DRAINS AT KITCHEN ICE MACHINE NOT APPROVED NOT DIRECTLY TRAPPED. BACK PITCH FILTER DRAIN TO HAVE AIR GAP. USE APPROVED STRAPS. | |
05/24/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE LISTING FOR ICE MAKER THAT SHOWS IT HAS BEEN TESTED UNDER ACTUAL BACKFLOW CONDITIONS, OR PROVIDE BACKFLOW PROTECTION DRAIN LINES MAY NOT BE COMBINED AND IF OVER FIVE FEET, TO BE DIRECTLY TRAPPED 2) INSTALL SIGN SHOWING LOCATION OF ANSUL VALVE ABOVE CEILING 3) MAKE ALL CONNECTIONS, SET ALL FIXTURES |