Permit: T04CM05370

Parcel: 133243720

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM05370

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/01/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/31/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) VDV SUPPORTS TO BE INDEPENDENTLY SUPPORTED -NOT ON CEILING SUPPORT WIRES 300.11. 2) FINISH HOOD INTERCONNECT. 3) PROPERLY IDENTIFY GROUNDING CONDUCTOR. 4) PLEASE VERIFY LISTING FOR PIZZA OVEN
03/28/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) FINISH ELECTRIC. 2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE IN NON COMBUSTIBLE AND FLUSH IN COMBUSTABLE TO USE APPROVED EXTENDER RINGS. 3) PLEASE VERIFY LISTING LABELS FOR EQUIPMENT. 4) TIGHTEN LOOSE FITTINGS. 5) ELECTRIC TO BE INDEPENDENTLY SUPPORTED. 6) VDV CABLES TO BE SUPPORTED 725.6. 7) FILL UNUSED OPENING IN BOX. 8) ATTACH FIXTURES TO GRID.