Permit: T04CM05356

Parcel: 11623049A


Addresses:

810 W 19TH ST

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
08/22/2005 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
1) 977-6717 AT STREET OIL
05/18/2005 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MUST SHADE PIPING IN PLACE THROUGHOUT
2) REMOVE ALL FOAM TO INSPECT PIPING
3) 2" LINE NOT TO BE RUN UNDERNEATH EXTERIOR FTG. (MOVE)
4) INSIDE FTG AND RUN PARALLEL TO IT
5) MAINTAIN 1/4" SLOPE THROUGHOUT
6) VENTS NOT PER PLAN
7) MAINTAIN 5 POUND AIR TEST OR H20 TEST THROUGHOUT
8) STOPPED INSPECTION