Permit: T04CM05352

Parcel: 12405051A


Addresses:

870 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Permit Number - T04CM05352

Inspection Description - PLUMBING - GAS PRESS TEST FNL

Inspection Status - Approved

Date Description Inspector Results Comments
01/19/2011 PLUMBING - GAS PRESS TEST FNL Approved
01/06/2011 PLUMBING - GAS PRESS TEST FNL Partial Approval IVRS - Inspection :*
1) TEST ON 1" FROM METER TO SHUT OFFS (3), (1) AT STOVE OVEN, (2) AT STACK PIZZA OVEN WITH FLEXES IN PLACE IS HOLDING WITHOUT THE LISTING PLATES THIS INSPECTOR CANNOT VERIFY SYSTEM IS SIZED FOR THE BTU'S DEMAND OF THESE APPLIANCES. THE INFORMATION PROVIDED ABOUT THE PIZZA OVENS REQUIRES 7" WC GAS, THIS IS NOT TYPICALLY POSSIBLE ON AN SYSTEM DESIGNED AT INCHES FROM S.W. GAS DELIVERY. PLEASE MAKE CONTACT WITH THE OVEN MANUFACTURE AND VEIRYF GAS INFORMATION AND IF 7" GAS IS REQUIRED MAKE CONTACT WITH S.W. GAS SERVICE PLANING AND YOU COULD BE REQUIRED TO CHANGE YOUR CITY APPROVED PLAN