Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
Permit Number - T04CM05352
Inspection Description - PLUMBING - GAS PRESS TEST FNL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2011 | PLUMBING - GAS PRESS TEST FNL | Approved | ||
01/06/2011 | PLUMBING - GAS PRESS TEST FNL | Partial Approval | IVRS - Inspection :* 1) TEST ON 1" FROM METER TO SHUT OFFS (3), (1) AT STOVE OVEN, (2) AT STACK PIZZA OVEN WITH FLEXES IN PLACE IS HOLDING WITHOUT THE LISTING PLATES THIS INSPECTOR CANNOT VERIFY SYSTEM IS SIZED FOR THE BTU'S DEMAND OF THESE APPLIANCES. THE INFORMATION PROVIDED ABOUT THE PIZZA OVENS REQUIRES 7" WC GAS, THIS IS NOT TYPICALLY POSSIBLE ON AN SYSTEM DESIGNED AT INCHES FROM S.W. GAS DELIVERY. PLEASE MAKE CONTACT WITH THE OVEN MANUFACTURE AND VEIRYF GAS INFORMATION AND IF 7" GAS IS REQUIRED MAKE CONTACT WITH S.W. GAS SERVICE PLANING AND YOU COULD BE REQUIRED TO CHANGE YOUR CITY APPROVED PLAN |