Permit: T04CM05338

Parcel: 130060010


Addresses:

1630 S ALVERNON WY

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/31/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/30/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* VENT ON CONDENSATE TRAP MUST BE DOWNSTREAM OF TRAP. INDIRECT TERMINATION IN ATTIC TO EXISTING DRAIN NOT TO CODE. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT PIPE. PERMANENTLY IDENTIFY EQUIPTMENT WITH UNIT NUMBER.