Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM05306
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/16/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/1)WALLS WIRED IN ROMEX-PROVIDE LETTER FROM ARCH. TO OK THIS TYPE OF INSTALLATION. PRIOR TO FINAL-OK ROMEX PER CODE AS INSTALLED. | |
| 12/14/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/1)WALLS COVERED PRIOR TO INSPECTION, ROMOVE 1-SIDE OF DRYWALL FOR INSPECTION 2)ROMEX TO BE SUPPORTED PER NEC USING APPROVED CLAMPS OR STAPLES, BENT NAILS NOT APPROVED METHOD OF SUPPORT. ROMEX CONNECTORS MUST BE CLAMPED TIGHT. 3)REMOVE CEILING TILES OVER HEAD TO INSPECT METHOD OF SUPPORT OF ROMEX OVERHEAD. VERIFY L-11 LICENSED CONTR. DOING WORK. HAVE CONTRACTOR CONTACT INSPECTOR AT 791-5550 #1136 PRIOR TO NEXT INSPECTION. |
|
| 12/09/2004 | ELECTRIC - INTERMEDIATE | Cancelled | BY ELIZA ALMAZON 883-2458-NOTIFIED RAY BY VOICE MSG | |
| 12/09/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/CANCEL PER RAY |